Battery Monitor Settings
110
900-0117-01-00 Rev A
Relay Set Points
This menu allows the user to adjust the criteria used by the Auto selection in the Relay Mode menu. For
more information on these criteria, see the
User’s Manual
for the battery monitor.
To
access
the
Relay Set Points
menu:
1.
Access the
Battery Monitor
menu as shown in Figure 106.
2.
Use the control wheel to highlight the
Relay Set Points
menu.
Press the button in the center of the control wheel to accept the selection.
3.
Use the control wheel to increase or decrease the set points to the correct voltage.
Press the button in the center of the control wheel to accept the selection.
This should automatically move the highlighting to the next set point.
4.
After setting the parameters for each set point, press the
TOP
navigation key to return to the
Main Menu
screen.
Figure 110 Relay Set Points
Set Points:
The following set points assume N.O. logic. If N.C. logic is used, all use of the words “close” or “open” are
reversed.
Voltage: High:
The relay will close upon reaching a specified high voltage level (following the
appropriate delay; see below).
(Voltage)
Low:
After the relay was closed according to the
High
voltage set point, it will open again
upon reaching a specified low voltage level (following the appropriate delay; see below).
SOC: High:
If voltage conditions are not met, the relay will close when the battery state of charge
(SOC) increases to a specified percentage (following the appropriate delay; see below).
(SOC)
Low:
After the relay was closed according to the
High
SOC set point, it will open again upon
reaching a specified low SOC level (following the appropriate delay; see below).
Delay: High:
Sets the delay time before the relay closes due to a
High
set point. This applies to either
the SOC or voltage settings.
(Delay)
Low:
Sets the delay time before the relay opens due to a
Low
set point. This applies to either
the SOC or voltage settings.
Summary of Contents for OutBack Power MATE3
Page 1: ...MATE3 System Display and Controller Owner s Manual ...
Page 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Page 159: ......