MATE3 Settings
132
900-0117-01-00 Rev A
FLEXnet DC Advanced Control
This menu allows certain advanced functions to be programmed into the FLEXnet DC. (The FLEXnet DC is
required to be part of the system before any of these functions can be used.)
To program FLEXnet DC Advanced Control:
1.
Access the
MATE
Menu as shown in Figure 113.
2.
Use the control wheel to select the
FLEXnet DC Advanced Control
menu option.
Press the button in the center of the control wheel to select the menu.
3.
Use the control wheel to increase or decrease the value for each set point.
Press the button in the center of the control wheel to enter the value.
When the value is entered, the highlighting will move forward to the next set point.
4.
After setting the parameters for each set point, press the
TOP
navigation key to return to the
Main Menu
screen.
Figure 129 FLEXnet DC Advanced Control
See the
FNDC User’s Guide
for detailed
information about the FNDC functions.
Set Points:
Enable Charge Termination Control
allows the battery charging to be turned
off for all inverters on the system, once
the FLEXnet’s charging parameters have
been met. (See page 107 for these
parameters.) Options are
N
(no) or
Y
(yes).
Enable Auto Grid-Tie Control
If grid-
interactive inverters are present on the
system, this function allows their grid-
interactive function to be turned off at
midnight each night. If grid-interactive
inverters are not present, this item is
inoperative. Options are
N
(no) or
Y
(yes).
The next two items are both related to the system indicators on the Home screen (see pages 25 and 141), and
are titled
Battery Status
on the screen.
Low SOC Warning Level
If the batteries decrease to this state of charge (SOC), an event will be registered
in the event log, and the Home screen will display
!
, a battery warning. Settable range is 20% - 99%.\
Critical SOC Warning Level
If the batteries decrease to this state of charge (SOC), an event will be
registered in the event log, and the Home screen will display
X
, a warning that the batteries have
been critically discharged. Settable range is
10% - 98%.
Summary of Contents for OutBack Power MATE3
Page 1: ...MATE3 System Display and Controller Owner s Manual ...
Page 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Page 159: ......