MATE3 Settings
114
900-0117-01-00 Rev A
Advanced Generator Start (AGS) Mode
CAUTION: Equipment Damage
This feature can damage the generator or the batteries if either are not properly
maintained. Be sure to follow all maintenance requirements for all the components in
the system to prevent unnecessary and expensive damage.
The AGS Mode utilizes the auxiliary (AUX) output on the inverter or charge controller (or the FLEXnet DC
relay output) and is compatible with any two-wire start generator.
AGS starts the generator any time when any of its Start conditions are met, and stops the generator when
any of its Stop conditions are met. A Quiet Time schedule overrides most of the Start conditions to keep
the generator from running at inappropriate hours.
NOTE:
If AGS mode controls the AUX output of a FLEXmax charge controller, that charge controller’s
Auxiliary Output
menu must be set to
Remote
for this function to work. (See page 103.)
AGS can start a generator under the following variety of settings:
Voltage Start
------------------------------------------------ >
Load Start
---------------------------------------------------- >
State of Charge % Start (FLEXnet DC)
-------------- >
Must Run Schedule
---------------------------------------- >
Quiet Time Schedule
------------------------------------- >
Exercise
------------------------------------------------------- >
Gen Alert
is another way to automatically start a generator, but it does not offer the same range of
programming options as AGS. AGS is a function of the MATE3 while
Gen Alert
is a function of the inverter,
which is programmed using the MATE3. Information on the
Gen Alert
function can be found in the
inverter
Operator’s Manual
.
Figure 114 Advanced Generator Start (AGS) Menu
Summary of Contents for OutBack Power MATE3
Page 1: ...MATE3 System Display and Controller Owner s Manual ...
Page 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Page 159: ......