Publication 1756-UM523F-EN-P - December 2006
Update Modules and Redundant Systems
139
Redundant System Relationships
Different terms are unique to normal redundancy and redundancy
during an update.
Complete this procedure to update the firmware of a redundant
chassis without shutting down the process.
IMPORTANT
When a secondary communications module is locking for
updating, it displays SLU. When a primary communications
module is locked for updating and has firmware revision 15.56
or later, it displays PLU. If the primary communications module’s
firmware is an earlier revision, PwQS will be displayed when
the system is locked.
This term in normal redundancy
Equates to this term during the updating of a
redundant system
Synchronize
Lock for Update
Synchronizing
Locking for Update
Synchronized
Locked for Update
Switchover
Locked Switchover
IMPORTANT
Use this procedure only if your system is already at revision 13.
Do not use this procedure if:
•
your system is at revision 11 or earlier.
•
your system is not operating yet.
During this procedure, you will not be able to use RSLogix 5000 software
to change the mode of the controller. Use the keyswitch on the front of
the controller to change its mode.
Leave RSNetWorx for ControlNet software closed or offline throughout
this procedure. Otherwise, you will see errors in the RSNetWorx
software during the update process.
During this procedure:
•
do not make any changes to the RSLogix 5000 project other than
the ones called out in this procedure.
•
make sure no one else makes changes to the project.
Summary of Contents for 1756-CNB/E
Page 4: ...Publication 1756 UM523F EN P December 2006 Summary of Changes 4 Notes...
Page 10: ...Publication 1756 UM523F EN P December 2006 10 Table of Contents...
Page 26: ...Publication 1756 UM523F EN P December 2006 26 ControlLogix Redundancy System Overview Notes...
Page 42: ...Publication 1756 UM523F EN P December 2006 42 Design the System Notes...
Page 64: ...Publication 1756 UM523F EN P December 2006 64 Configure the System Redundancy Module Notes...
Page 102: ...Publication 1756 UM523F EN P December 2006 102 Configure and Program the Controller Notes...
Page 146: ...Publication 1756 UM523F EN P December 2006 146 Update Modules and Redundant Systems Notes...
Page 168: ...Publication 1756 UM523F EN P December 2006 168 Convert an Existing System to Redundancy Notes...
Page 178: ...Publication 1756 UM523F EN P December 2006 178 Redundant System Restrictions Notes...
Page 185: ......