Publication 1756-UM523F-EN-P - December 2006
52
Install the System
Actions
1.
Turn on the chassis power to the partner (secondary) chassis.
2.
Wait for the 1757-SRM module to complete its power-up cycle.
•
The SRM module takes 1...3 minutes to power up.
•
It may also take several minutes to synchronize the secondary
controller.
•
Does 1 of the 1757-SRM modules show PRIM and the other
module show SYNC?
•
Yes — Stop. The system is synchronized.
•
No — There is a problem. The system is not synchronized.
Go to step 3.
3.
Make sure that the Auto-Synchronization option of the SRMs is
set to Always. For help, see Chapter 4.
•
Does 1 of the 1757-SRM modules show PRIM and the other
module show SYNC?
•
Yes— Stop. The system is synchronized.
•
No— Go to Troubleshoot a Failure to Synchronize on page
105.
Redundancy Module
PRI COM OK
42801
PRIM
Redundancy Module
PRI COM OK
SYNC
First Chassis
Turned On
Second Chassis
Turned On
Redundancy Module
PRI COM OK
PRIM
Redundancy Module
PRI COM OK
SYNC
Summary of Contents for 1756-CNB/E
Page 4: ...Publication 1756 UM523F EN P December 2006 Summary of Changes 4 Notes...
Page 10: ...Publication 1756 UM523F EN P December 2006 10 Table of Contents...
Page 26: ...Publication 1756 UM523F EN P December 2006 26 ControlLogix Redundancy System Overview Notes...
Page 42: ...Publication 1756 UM523F EN P December 2006 42 Design the System Notes...
Page 64: ...Publication 1756 UM523F EN P December 2006 64 Configure the System Redundancy Module Notes...
Page 102: ...Publication 1756 UM523F EN P December 2006 102 Configure and Program the Controller Notes...
Page 146: ...Publication 1756 UM523F EN P December 2006 146 Update Modules and Redundant Systems Notes...
Page 168: ...Publication 1756 UM523F EN P December 2006 168 Convert an Existing System to Redundancy Notes...
Page 178: ...Publication 1756 UM523F EN P December 2006 178 Redundant System Restrictions Notes...
Page 185: ......