Publication 1756-UM523F-EN-P - December 2006
Set Up EtherNet/IP Communication Across Subnets
155
To keep a Message (MSG) instruction going to the new primary
chassis after a switchover:
•
create a periodic trigger for the messages.
•
obtain the redundancy state of chassis A.
•
obtain the redundancy state of chassis B.
•
determine which chassis is primary.
•
send the message to the appropriate controller.
Create a Periodic Trigger for the Messages
E
N
B
L
x
E
N
B
L
5
5
Chassis B
MSG
Type - CIP Generic
MSG
Type - CIP Generic
E
N
B
T
L
5
5
M
Chassis A
Free-running timer that triggers the execution of MSG instructions. The timer runs for 2 seconds (2000 ms) and then resets
and starts timing again. Every 2 seconds, Timer_RedundancyMSGs.DN = 1 for a single scan. The MSG instructions use this
bit as one of their conditions for execution.
Tag Name
Description
Alias For
Data Type
Timer_RedundancyMSGs
Periodic trigger for the
execution of MSG
instructions. Triggers MSGs
every 2 s.
TIMER
Summary of Contents for 1756-CNB/E
Page 4: ...Publication 1756 UM523F EN P December 2006 Summary of Changes 4 Notes...
Page 10: ...Publication 1756 UM523F EN P December 2006 10 Table of Contents...
Page 26: ...Publication 1756 UM523F EN P December 2006 26 ControlLogix Redundancy System Overview Notes...
Page 42: ...Publication 1756 UM523F EN P December 2006 42 Design the System Notes...
Page 64: ...Publication 1756 UM523F EN P December 2006 64 Configure the System Redundancy Module Notes...
Page 102: ...Publication 1756 UM523F EN P December 2006 102 Configure and Program the Controller Notes...
Page 146: ...Publication 1756 UM523F EN P December 2006 146 Update Modules and Redundant Systems Notes...
Page 168: ...Publication 1756 UM523F EN P December 2006 168 Convert an Existing System to Redundancy Notes...
Page 178: ...Publication 1756 UM523F EN P December 2006 178 Redundant System Restrictions Notes...
Page 185: ......