Publication 1756-UM523F-EN-P - December 2006
112
Maintain and Troubleshoot the System
4. Double-click and event for more
information.
A. Double-click an event to see if it gives more information.
The Extended Information Definition dialog opens.
B. Click OK when you are done to close the Extended Information Definition dialog.
Example
5. If the secondary log does not show the
cause, look at the primary log.
Sometimes you have to use both logs to find out what happened.
Example
Action
Details
Someone removed the module for slot 2. Or the
module failed.
•
The secondary log shows that something
happened around 15:40. But it is not clear
just what happened.
•
The primary log shows that around that
time the partner SRM screamed. That
means it lost power.
Summary of Contents for 1756-CNB/E
Page 4: ...Publication 1756 UM523F EN P December 2006 Summary of Changes 4 Notes...
Page 10: ...Publication 1756 UM523F EN P December 2006 10 Table of Contents...
Page 26: ...Publication 1756 UM523F EN P December 2006 26 ControlLogix Redundancy System Overview Notes...
Page 42: ...Publication 1756 UM523F EN P December 2006 42 Design the System Notes...
Page 64: ...Publication 1756 UM523F EN P December 2006 64 Configure the System Redundancy Module Notes...
Page 102: ...Publication 1756 UM523F EN P December 2006 102 Configure and Program the Controller Notes...
Page 146: ...Publication 1756 UM523F EN P December 2006 146 Update Modules and Redundant Systems Notes...
Page 168: ...Publication 1756 UM523F EN P December 2006 168 Convert an Existing System to Redundancy Notes...
Page 178: ...Publication 1756 UM523F EN P December 2006 178 Redundant System Restrictions Notes...
Page 185: ......