Publication 1756-UM523F-EN-P - December 2006
96
Configure and Program the Controller
b. Choose Advanced.
4.
Browse to the controller in the primary chassis.
5.
Select the controller and choose Download.
The Download diaglog opens.
6.
Choose Download.
c. Leave unchecked Match
Project to Controller.
IMPORTANT
If you match your downloaded project to your controller, you tie
your project to your controller’s serial number. If you then
switch over to a controller in a different chassis, your project
will not match the new controller’s serial number, disabling the
controller functions originally specified under the Advanced tab
of Controller Properties
A. Open a branch in one of these ways:
•
Double-click it.
•
Click its + sign.
•
Select it and press the
→
key.
B. Find the primary chassis. Its communication
module uses the address that you gave it.
Workstation
Linx Gateways, Ethernet
My_Network
n, 1756 communication module
Backplane, 1756-Ax
C. Find the controller.
xx, 1756 controller
−
+
−
−
−
Summary of Contents for 1756-CNB/E
Page 4: ...Publication 1756 UM523F EN P December 2006 Summary of Changes 4 Notes...
Page 10: ...Publication 1756 UM523F EN P December 2006 10 Table of Contents...
Page 26: ...Publication 1756 UM523F EN P December 2006 26 ControlLogix Redundancy System Overview Notes...
Page 42: ...Publication 1756 UM523F EN P December 2006 42 Design the System Notes...
Page 64: ...Publication 1756 UM523F EN P December 2006 64 Configure the System Redundancy Module Notes...
Page 102: ...Publication 1756 UM523F EN P December 2006 102 Configure and Program the Controller Notes...
Page 146: ...Publication 1756 UM523F EN P December 2006 146 Update Modules and Redundant Systems Notes...
Page 168: ...Publication 1756 UM523F EN P December 2006 168 Convert an Existing System to Redundancy Notes...
Page 178: ...Publication 1756 UM523F EN P December 2006 178 Redundant System Restrictions Notes...
Page 185: ......