Publication 1756-UM523F-EN-P - December 2006
72
Configure and Program the Controller
Configure Message (MSG) Instructions
Configured Message Instructions
If the MSG instruction
is
Then
From a redundant
controller
In a redundant controller, any MSG instruction that is in progress during a switchover experiences an error.
(The ER bit of the instruction turns on.) After the switchover, normal communication resumes.
To a redundant controller
For any MSG instruction from a controller in another chassis to a redundant controller, cache the connection:
42977
Leave this box checked.
Path to the
Redundant
Controller.
Properties of the Message to the Redundant Controller
If the MSG instruction
originates from a
redundant controller
Then
During a switchover
The message instructions status bits are updated asynchronously to the program scan. Consequently, you
cannot crossload your message instructions status bits to a secondary controller.
During a switchover, any active message instructions become inactive. When this occurs, you will need to
reinitialize the execution of your message instructions in the new primary controller.
During qualification
The scrolling display changes from CMPT for compatible to Qfng for qualifying.
•
If a configured message is cached, the primary controller automatically establishes a connection with no
errors.
•
If a configured message is uncached or unconnected, the primary controller receives
Error 1 Extended
Error 301, No Buffer Memory
.
Summary of Contents for 1756-CNB/E
Page 4: ...Publication 1756 UM523F EN P December 2006 Summary of Changes 4 Notes...
Page 10: ...Publication 1756 UM523F EN P December 2006 10 Table of Contents...
Page 26: ...Publication 1756 UM523F EN P December 2006 26 ControlLogix Redundancy System Overview Notes...
Page 42: ...Publication 1756 UM523F EN P December 2006 42 Design the System Notes...
Page 64: ...Publication 1756 UM523F EN P December 2006 64 Configure the System Redundancy Module Notes...
Page 102: ...Publication 1756 UM523F EN P December 2006 102 Configure and Program the Controller Notes...
Page 146: ...Publication 1756 UM523F EN P December 2006 146 Update Modules and Redundant Systems Notes...
Page 168: ...Publication 1756 UM523F EN P December 2006 168 Convert an Existing System to Redundancy Notes...
Page 178: ...Publication 1756 UM523F EN P December 2006 178 Redundant System Restrictions Notes...
Page 185: ......