Redundant System Restrictions
Introduction
This appendix explains the known restrictions affecting a redundant
system.
Redundant System
Restrictions
There are several restricted features and functions in a redundant
system.
Do not use any of these features in a ControlLogix redundancy
system.
•
Local chassis I/O, 1756-DHRIO, or 1756-DNB modules.
•
Event task.
•
Inhibit a task.
•
Motion control, such as these modules:
–
1756-HYD02
–
1756-L60M03SE
–
1756-M02AE
–
1756-M02AS
–
1756-M03SE
–
1756-M08SE
–
1756-M16SE
IMPORTANT
In a redundant system, use an EtherNet/IP network only for
HMI/workstation communication and messaging.
Do not use an EtherNet/IP network for:
•
communication with I/O modules.
•
communication between devices via produced/consumed
tags.
Summary of Contents for 1756-CNB/E
Page 4: ...Publication 1756 UM523F EN P December 2006 Summary of Changes 4 Notes...
Page 10: ...Publication 1756 UM523F EN P December 2006 10 Table of Contents...
Page 26: ...Publication 1756 UM523F EN P December 2006 26 ControlLogix Redundancy System Overview Notes...
Page 42: ...Publication 1756 UM523F EN P December 2006 42 Design the System Notes...
Page 64: ...Publication 1756 UM523F EN P December 2006 64 Configure the System Redundancy Module Notes...
Page 102: ...Publication 1756 UM523F EN P December 2006 102 Configure and Program the Controller Notes...
Page 146: ...Publication 1756 UM523F EN P December 2006 146 Update Modules and Redundant Systems Notes...
Page 168: ...Publication 1756 UM523F EN P December 2006 168 Convert an Existing System to Redundancy Notes...
Page 178: ...Publication 1756 UM523F EN P December 2006 178 Redundant System Restrictions Notes...
Page 185: ......