Publication 1756-UM523F-EN-P - December 2006
Maintain and Troubleshoot the System
111
3. Look through the events of the secondary
chassis for a substantial change in log
times.
A. Start with the secondary chassis.
•
The lower list is the secondary chassis.
•
The cause of the switchover probably happened to secondary chassis while it was
the primary chassis.
B. Look for a change of months, days, or hours between the log times of events.
•
Sometimes the difference is only minutes.
•
The SRM logs only significant events. It does not log events while your system is
running normally.
C. Use the slot and module columns to find the module that caused the event.
D. Go to Interpret SRM events on page 113 to interpret the description.
Example
Action
Details
Here is a substantial change
in the log time.
The slot, module, and
description columns show
that the 1756-EWEB module
in slot 2 went lonely. That
usually means it lost its
network connection.
Summary of Contents for 1756-CNB/E
Page 4: ...Publication 1756 UM523F EN P December 2006 Summary of Changes 4 Notes...
Page 10: ...Publication 1756 UM523F EN P December 2006 10 Table of Contents...
Page 26: ...Publication 1756 UM523F EN P December 2006 26 ControlLogix Redundancy System Overview Notes...
Page 42: ...Publication 1756 UM523F EN P December 2006 42 Design the System Notes...
Page 64: ...Publication 1756 UM523F EN P December 2006 64 Configure the System Redundancy Module Notes...
Page 102: ...Publication 1756 UM523F EN P December 2006 102 Configure and Program the Controller Notes...
Page 146: ...Publication 1756 UM523F EN P December 2006 146 Update Modules and Redundant Systems Notes...
Page 168: ...Publication 1756 UM523F EN P December 2006 168 Convert an Existing System to Redundancy Notes...
Page 178: ...Publication 1756 UM523F EN P December 2006 178 Redundant System Restrictions Notes...
Page 185: ......