Publication 1756-UM523F-EN-P - December 2006
Configure and Program the Controller
101
3. Determine the real scan time of a task.
Complete these steps while the controller is running.
4. See if the watchdog time is big enough.
A. Calculate the smallest watchdog time for your task using the real scan time of the task:
Smallest watchdog time
=
(2 *
maximum_scan_time
) + 150 ms
B. Is your watchdog time more than the smallest watchdog time from step 4A above?
•
Yes — Stop. Your watchdog time is OK.
•
No — Repeat step 2 and enter a new watchdog time.
Action
Details
Longest time it has taken in
microseconds to scan this task.
C. Look at the scan times.
B. Click Monitor.
D. If you want to clear the Max counters and
start over, click Reset.
Controller Primary
Tasks
MainTask
+
−
+
A. Right-click the task and choose Properties.
Time it took in microseconds to scan this
task the last time it ran.
E. Choose OK.
Summary of Contents for 1756-CNB/E
Page 4: ...Publication 1756 UM523F EN P December 2006 Summary of Changes 4 Notes...
Page 10: ...Publication 1756 UM523F EN P December 2006 10 Table of Contents...
Page 26: ...Publication 1756 UM523F EN P December 2006 26 ControlLogix Redundancy System Overview Notes...
Page 42: ...Publication 1756 UM523F EN P December 2006 42 Design the System Notes...
Page 64: ...Publication 1756 UM523F EN P December 2006 64 Configure the System Redundancy Module Notes...
Page 102: ...Publication 1756 UM523F EN P December 2006 102 Configure and Program the Controller Notes...
Page 146: ...Publication 1756 UM523F EN P December 2006 146 Update Modules and Redundant Systems Notes...
Page 168: ...Publication 1756 UM523F EN P December 2006 168 Convert an Existing System to Redundancy Notes...
Page 178: ...Publication 1756 UM523F EN P December 2006 178 Redundant System Restrictions Notes...
Page 185: ......