Publication 1756-UM523F-EN-P - December 2006
108
Maintain and Troubleshoot the System
4.
Make sure that each node has a valid keeper signature.
5.
Choose Close.
Edit Sessions in Progress
To see if a computer is stopping the secondary chassis from
synchronizing, you must see if an edit session is in progress.
To edit sessions in progress, perform this procedure when a
secondary chassis will not synchronize and the CNB modules in the
secondary chassis show CMPT.
Actions
If the Valid Keeper column shows
Then
Yes
The node has a valid keeper signature.
No
Select the node and choose Update Keeper.
Secondary Chassis
42797
CMPT
Action
Details
1. Open the SRM configuration tool for the
primary chassis.
A. Start RSLinx software.
B. From the Communications menu, choose RSWho.
C. Open the branches of your network until you find the 1757-SRM module in the primary
chassis.
D. Right-click the SRM and choose Module Configuration.
Summary of Contents for 1756-CNB/E
Page 4: ...Publication 1756 UM523F EN P December 2006 Summary of Changes 4 Notes...
Page 10: ...Publication 1756 UM523F EN P December 2006 10 Table of Contents...
Page 26: ...Publication 1756 UM523F EN P December 2006 26 ControlLogix Redundancy System Overview Notes...
Page 42: ...Publication 1756 UM523F EN P December 2006 42 Design the System Notes...
Page 64: ...Publication 1756 UM523F EN P December 2006 64 Configure the System Redundancy Module Notes...
Page 102: ...Publication 1756 UM523F EN P December 2006 102 Configure and Program the Controller Notes...
Page 146: ...Publication 1756 UM523F EN P December 2006 146 Update Modules and Redundant Systems Notes...
Page 168: ...Publication 1756 UM523F EN P December 2006 168 Convert an Existing System to Redundancy Notes...
Page 178: ...Publication 1756 UM523F EN P December 2006 178 Redundant System Restrictions Notes...
Page 185: ......