43
Publication 1756-UM523F-EN-P - December 2006
Chapter
3
Install the System
Introduction
This chapter explains how to install the hardware of a ControlLogix
redundancy system.
Preliminary Information
Topic
Page
Preliminary Information
43
Install the Chassis for the Controllers
45
Install Modules in the First Redundant Chassis
46
Install Modules in the Second Redundant Chassis
48
Install the Remote Chassis or Rails
49
Configure EtherNet/IP Modules
50
Flash the Modules
51
Check the Installation
51
IMPORTANT
Use of the Network Access Port (NAP)
Do not connect any device to the network access port (NAP) of
a 1756-CNB/D/E or 1756-CNBR/D/E module in a redundant
chassis.
•
If you connect a device to the NAP of a CNB module in a
redundant chassis, a switchover will fail to occur if the CNB
module is disconnected from the network. While the CNB
module is disconnected from the network, the controller
will be unable to control any I/O devices through that CNB
module.
•
If you connect a workstation to the NAP of a CNB module in
a redundant chassis, the workstation will be unable to go
online after a switchover.
To connect a device to a ControlNet network via a NAP, use a
NAP that is outside of a redundant chassis.
Summary of Contents for 1756-CNB/E
Page 4: ...Publication 1756 UM523F EN P December 2006 Summary of Changes 4 Notes...
Page 10: ...Publication 1756 UM523F EN P December 2006 10 Table of Contents...
Page 26: ...Publication 1756 UM523F EN P December 2006 26 ControlLogix Redundancy System Overview Notes...
Page 42: ...Publication 1756 UM523F EN P December 2006 42 Design the System Notes...
Page 64: ...Publication 1756 UM523F EN P December 2006 64 Configure the System Redundancy Module Notes...
Page 102: ...Publication 1756 UM523F EN P December 2006 102 Configure and Program the Controller Notes...
Page 146: ...Publication 1756 UM523F EN P December 2006 146 Update Modules and Redundant Systems Notes...
Page 168: ...Publication 1756 UM523F EN P December 2006 168 Convert an Existing System to Redundancy Notes...
Page 178: ...Publication 1756 UM523F EN P December 2006 178 Redundant System Restrictions Notes...
Page 185: ......