6. Keep code as compact as possible.
Avoid checking the same conditions many times. Each instruction adds scan time to your
controller.
Action
Details
This is better
This rung checks Bool_B and Bool_C only once each scan.
Than this
This rung checks Bool_B and Bool_C twice each scan. One or two instructions do not add much
scan time. But if you do this often, the extra instructions add up to a much longer scan time.