Update Modules and Redundant Systems
143
11. Change the project revisions.
B. Click the Controller Properties button.
C. Change the controller to the newer revision.
Example
: Change the controller from revision 13 to revision 15.
D. Change the Revision of each local communication module to match what its revision
will be after you update its firmware.
Example:
Suppose you plan to update the firmware of each CNB/D module in the
redundant chassis to revision 7.12. In that case, open the properties for each CNB/D
module in the chassis and set the revision to 7.12.
If you cannot select the new revision, then change the electronic keying to either
compatible keying or disable keying.
Action
Details
A. Go offline.
Summary of Contents for 1756-CNB/E
Page 4: ...Publication 1756 UM523F EN P December 2006 Summary of Changes 4 Notes...
Page 10: ...Publication 1756 UM523F EN P December 2006 10 Table of Contents...
Page 26: ...Publication 1756 UM523F EN P December 2006 26 ControlLogix Redundancy System Overview Notes...
Page 42: ...Publication 1756 UM523F EN P December 2006 42 Design the System Notes...
Page 64: ...Publication 1756 UM523F EN P December 2006 64 Configure the System Redundancy Module Notes...
Page 102: ...Publication 1756 UM523F EN P December 2006 102 Configure and Program the Controller Notes...
Page 146: ...Publication 1756 UM523F EN P December 2006 146 Update Modules and Redundant Systems Notes...
Page 168: ...Publication 1756 UM523F EN P December 2006 168 Convert an Existing System to Redundancy Notes...
Page 178: ...Publication 1756 UM523F EN P December 2006 178 Redundant System Restrictions Notes...
Page 185: ......