Publication 1756-UM523F-EN-P - December 2006
Update Modules and Redundant Systems
133
7. Update the keeper signatures of the CNB
modules.
A. Start RSNetWorx for ControlNet and open the network configuration file.
B. Go online with the network. You do not have to browse the entire network.
C. Select Network > Keeper Status.
D. Select the node number of the secondary CNB and click Update Keeper.
E. Verify that the keeper signature has been updated.
F. Repeat steps D and E for the other CNB modules in the secondary chassis.
G. Click Close.
Action
Details