2-1
PRODUCT DATA SHEET
SM CKDDCI 2-A.3 GB
2.
PRODUCT DATA SHEET
2.1
CKD 036 DCI / GCD 036 DCR
Model Indoor Unit
CKD 036 DCI
Model Outdoor Unit
GCD 036 DCR
Installation Method
CASSETTE
Characteristics
Units
Cooling
Heating
Capacity - Nominal (Minimum ~ Maximum)
(1)
Btu/hr
30,700 (8,900 – 34,120) 35,150 (8,200 – 39,250)
kW
9.0 (2.6 – 10.0)
10.3 (2.4 – 11.5)
Power Input - Nominal (Minimum ~ Maximum)
( (1)
W
3,100 (750 – 3,850)
3,430 (520 – 3,960)
EER (Cooling) / COP (Heating)
(1)
W/W
2.9
3.0
Energy Efficiency Class
-
“C”
“D”
Power Supply
V/Ph/Hz
220-240/1/50
Rated Current (Nominal)
A
13.0
14.4
Starting Current
A
<10
Circuit Breaker Rating
A
25
INDOOR
Fan Type & Quantity
CENTRIFUGAL x1
Fan Speed
H/M/L
RPM
580
540
500
Airflow
(2)
H/M/L
m
3
/hr
1170
1080
990
External Static Pressure
Min-Nom-Max
Pa
-
Sound Power Level
(3)
H/M/L
dB (A)
44
42
40
Sound Pressure Level
(4)
H/M/L
dB (A)
53
51
49
Moisture Removal (Nominal)
L/hr
3.7
Condensate Drain Tube I.D.
mm
19
Dimensions
W/H/D
mm
840
300
840
Weight
kg
32(+6kf Panel)
Package Dimensions
W/H/D
mm
950
317
950
Packaged Weight
kg
40(+6kg Panel)
Units per Pallet
Units
6
Stacking Height
Units
6
OUTDOOR
Refrigerant Control
Electronic Expansion Valve
Compressor Type, Model
Scroll
Motor type
DCBL Inverter
Fan Type & Quantity
Axial 2x 400
Ф
mm
Fan Speed
RPM
1100-100 (continuous)
Airflow
Max
m
3
/hr
4,150
Sound Power Level
Nom C/H
dB (A)
67
69
Sound Pressure Level
(4)
Nom C/H
dB (A)
57
59
Dimensions
W/H/D
mm
900
970
340
Weight
kg
76
Package Dimensions
W/H/D
mm
985
1020
435
Packaged Weight
kg
81
Units per Pallet
Units
6
Stacking Height
Units
2
Refrigerant Type
R410A
Refrigerant Charge (STD connected Tube
Length)
kg (m)
2.5 / 30
Additional Charge
g/m
30
Connections
Between Units
Liquid Line
In (mm)
3/8”
Suction Line
In (mm)
5/8”
Max. Tubing Length
m
70
Max. Height Difference
m
30
Operation Control Type
LCD Remote Control
Heating Elements
kW
BH 70W - optional
Others
(1)
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2)
Airflow in ducted units; at nominal external static pressure.
(3)
Sound power in ducted units is measured at air discharge.
(4)
Sound pressure level measured at 1.0 meter distance from unit.