Quick Start Guide
FUSION-TEC
®
/LV1000 Air Conditioning System
SYSTEM SET-UP
Set up and configuration must be done to each wall-
mount unit using the TEC-EYE hand-held diagnostic tool.
Use the LV1000 controller for the remaining steps.
IMPORTANT:
When working with circuit board
components, Bard recommends the use of
an anti-static wrist strap to prevent static
electricity shorts to electronic controls.
Address each wall unit and select unit of measure (UOM)
and economizer control type (TEC-EYE)
The address of the unit being looked at will be listed in
the upper right hand corner on the status screen. The
available addresses are 1-4.
1. Connect TEC-EYE
TM
to wall-mount unit.
2. Press MENU key to access the Main Menu screen.
3. Press UP or DOWN keys and ENTER key to enter
password 1313.
4. Press UP or DOWN keys to scroll to
Sys Config
; press
ENTER key.
5. Press UP or DOWN keys to scroll to
Unit Setup (A1)
screen.
6. Press ENTER key to scroll to
Unit Address.
7. Press UP or DOWN keys to change address to value
between 1 and 4.
NOTE:
Each unit must have a unique address for the
communication to work properly. Bard also
recommends labeling each unit for ease in
identification.
8. Press ENTER key to save and scroll to
UOM
.
9. If desired, press UP or DOWN keys to change the
value from
USA
to
SI
,
NC
,
LON
,
CAN
or
UK
. Units
are preconfigured for each selection.
10. Press ENTER key to save and move the cursor back
to the top left position.
11. Press DOWN key to navigate to
Economizer Setup
(A2)
screen.
12. Press ENTER key to scroll to
Type
.
13. Press UP or DOWN keys to change economizer type to
None
,
Drybulb
,
Temperature and Humidity
or
Enthalpy
.
14. Press ENTER key to save and move the cursor back
to the top left position.
Execute a run test on each unit to verify the equipment is
functioning correctly (TEC-EYE)
1. Use UP or DOWN keys to scroll to
Run Test (A10)
screen.
2. Press ENTER key to scroll to
Run Test Enable
parameter.
3. Use UP or DOWN key to change value to
ON
. The run
test will begin and the screen will change to
Run Test
Summary
.
4. Press UP or DOWN key to scroll between
Run Test
Summary
,
Motors & Sensors
and
A/C Circuit
screens.
See Installation Instructions 2100-674 if additional
information on run testing units is needed.
Clear unit alarm logs (TEC-EYE)
To clear the wall-mount unit alarm logs:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
password 1313.
3. Press UP or DOWN keys to scroll to
Settings
; press
ENTER key.
4. Press UP or DOWN keys to scroll to
Initialization
;
press ENTER key.
5. Press ENTER key to scroll to
Clear Alarm Logs?
6. Press UP or DOWN key to change value to
YES
; press
ENTER key.
7. Press ESCAPE key several times to return to Main
Menu screen.
Manual 2100-675D
Date 2-20-19
This quick start guide is designed to lead the installer
through the steps necessary for setting up the FUSION-
TEC/LV1000 Free Cooling Unit System. See the latest
versions of FUSION-TEC/LV1000 System Installation
Instructions 2100-674, FUSION-TEC Service Instructions
2100-694 and LV1000 Service Instructions 2100-673
for more detailed information on the installation, service
and maintenance of the FUSION-TEC/LV1000 system.
The LV1000 controller and TEC-EYE
TM
hand-held
diagnostic tool will both be used in this installation. The
TEC-EYE diagnostic tool is shipped inside the controller.
Use password 1313.
It is important to check the software version
during installation to ensure that the latest
version has been installed. Current software
versions, change log and installation
instructions are available on the Bard website at
http://www.bardhvac.com/software-download/
NOTICE