12-33
CONTROL SYSTEM
SM CKDDCI 2-A.3 GB
12.8.2.5 Presence Detector/DIP – J9
Position Status
Description
0
Open (Disconnected)
Presence detector enabled (Default)
1
Close (Shorted)
NA (Not to be used)
12.8.3 ODU
Jumpers
12.8.3.1 Self test Jumper/DIP – J1
Position Status
Description
0
Open (Disconnected)
Normal Operation (Default)
1
Close (Shorted)
Self Test enabled
Used for internal production line testing. For normal use must be set to OFF (0).
12.8.3.2 ODU Model Selection Jumper/DIP – J2, J3, J4, J5, J6
ODU Model
J2
J3
J4
J5
J6
M (DCI 100)
ON
OFF
ON
ON
OFF
N (DCI 125)
OFF
ON
ON
ON
OFF
O (DCI 140)
ON
ON
ON
ON
OFF
AB (DCR100)
OFF
OFF
ON
ON
ON
12.8.3.3 TPT test Jumper/DIP – J8
Position Status
Description
0
Open (Disconnected)
Normal Operation (Default)
1
Close (Shorted)
Test enabled
Used for technician testing – TPT. For normal use must be set to OFF (0).