2-2
PRODUCT DATA SHEET
SM CKDDCI 2-A.3 GB
2.2
CKD 045 DCI / GC 43 DCI
Model Indoor Unit
CKD 045 DCI
Model Outdoor Unit
GC 43 DCI
Installation Method
CASSETTE
Characteristics
Units
Cooling
Heating
Capacity - Nominal (Minimum ~ Maximum)
(1)
Btu/hr
41,300 (8,550 – 44,350) 46,050 (8,850 – 49,150)
kW
12.1 (2.5 – 13.0)
13.5 (2.6 – 14.4)
Power Input - Nominal (Minimum ~ Maximum)
( (1)
W
4,400 (1,400 – 5,150)
4,800 (950 – 5,600)
EER (Cooling) / COP (Heating)
(1)
W/W
2.75
2.8
Energy Efficiency Class
-
“D”
“D”
Power Supply
V/Ph/Hz
220-230/1/50
Rated Current (Nominal)
A
19.5
21.3
Starting Current
A
<10
Circuit Breaker Rating
A
32
INDOOR
Fan Type & Quantity
CENTRIFUGAL x1
Fan Speed
H/M/L
RPM
810
650
590
Airflow
(2)
H/M/L
m
3
/hr
1,600
1,330
1,200
External Static Pressure
Min-Nom-Max
Pa
-
Sound Power Level
(3)
H/M/L
dB (A)
63
57
53
Sound Pressure Level
(4)
H/M/L
dB (A)
53
47
43
Moisture Removal (Nominal)
L/hr
5.4
Condensate Drain Tube I.D.
mm
19
Dimensions
W/H/D
mm
840
300
840
Weight
kg
32(+6kg Panel)
Package Dimensions
W/H/D
mm
950
317
950
Packaged Weight
kg
40(+6kg Panel)
Units per Pallet
Units
6
Stacking Height
Units
6
OUTDOOR
Refrigerant Control
Electronic Expansion Valve
Compressor Type, Model
Scroll
Motor type
DCBL Inverter
Fan Type & Quantity
Axial 2x 493
Ф
mm
Fan Speed
RPM
900-100 (continuous)
Airflow
Max
m
3
/hr
5,700
Sound Power Level
Nom C/H
dB (A)
69
70
Sound Pressure Level
(4)
Nom C/H
dB (A)
56
58
Dimensions
W/H/D
mm
900
1255
340
Weight
kg
110
Package Dimensions
W/H/D
mm
985
1395
435
Packaged Weight
kg
120
Units per Pallet
Units
3
Stacking Height
Units
1
Refrigerant Type
R410A
Refrigerant Charge (STD connected Tube
Length)
kg (m)
3.1 / 30
Additional Charge
g/m
40
Connections
Between Units
Liquid Line
In (mm)
3/8”
Suction Line
In (mm)
3/4”
Max. Tubing Length
m
70
Max. Height Difference
m
30
Operation Control Type
LCD Remote Control
Heating Elements
kW
BH 70W - optional
Others
(1)
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2)
Airflow in ducted units; at nominal external static pressure.
(3)
Sound power in ducted units is measured at air discharge.
(4)
Sound pressure level measured at 1.0 meter distance from unit.