7-1
ELECTRICAL DATA
SM CKDDCI 2-A.3 GB
7.
ELECTRICAL DATA
7.1
Single Phase Units
MODEL
GCD 036 DCR
GC 43 DCI
Power Supply
1PH – 230V – 50 Hz
Connected to
(a)
Outdoor
Indoor
Outdoor
Indoor
Max Current
23A
5A
28A
5A
Inrush Current
(c)
30A
Starting Current
(d)
10A
Circuit Breaker
25A
10A
32A
10A
Power Supply Wiring
No. X Cross Section
3 X 4.0 mm
2
3 X 1.5 mm
2
3 X 6.0 mm
2
3 X 1.5 mm
2
Interconnecting Cable
No. X Cross Section
(b)
3 X 1.5 mm
2
+
2 X 0.75 mm
2
(Communications)
2 X 0.75 mm
2
(Communications)
3 X 1.5 mm
2
+
2 X 0.75 mm
2
(Communications)
2 X 0.75 mm
2
(Communications)
(a) Power supply can be connected in both ways:
To outdoor unit to supply both outdoor and indoor unit.
To outdoor unit and to Indoor unit separately.
(b) Communication wires must be separated from the power wires and should be shielded type, earth connectedat
both ends.
(c) Inrush current is the current when power is up (charging the DC capacitors at outdoor unit controller).
(d) Starting current is the current peak when starting the compressor.
NOTE
:
Power wiring cord should comply with local lows and electrical regulations requirements.