12-32
CONTROL SYSTEM
SM CKDDCI 2-A.3 GB
12.8 Jumper/DIP-Switch
Setting
12.8.1 Jumper/DIP-Switch
Definition
0 = Open (Disconnected)
1 = Close (Shorted)
12.8.2 IDU
Jumpers/DIP-Switch
DNG / EMD / CD / NFC
NKN
12.8.2.1 Self test Jumper/DIP – J1
Position Status
Description
0
Open (Disconnected)
Normal Operation (Default)
1
Close (Shorted)
Self Test enabled
Used for internal production line testing. For normal use must be set to OFF (0).
12.8.2.2 Compensation Jumper/DIP – J2
Position Status
Description
0
Open (Disconnected)
Compensation deactivated
1
Close (Shorted)
Compensation activated (Default)
Used for height compenstation in heat mode
12.8.2.3 Family selection Jumper/DIP – J3, J4, J5, J11
#
Family Name
J3
J4
J5
J11
DNG 4-5 HP
1
1
0
NA
EMD 4-5 HP
0
1
0
NA
CD 6 HP
1
0
1
NA
NFC 4-5-6HP
0
1
1
NA
NKN 4-5HP
NA
NA
NA
1
12.8.2.4 Model selection Jumper/DIP – J7, J8
12.8.2.4.1 DNG / EMD / CD / NFC
Model
J7
J8
A – 4HP
0
0
B – 5HP
1
0
C – 6HP
0
1
12.8.2.4.2 NKN
Model
J7
J8
C – 4HP
0
1
D – 5HP
1
1