62
EXPERT LA rev.00
EXPERT LA
7.
HEATING
The controller can control up to 8 independent heat-
ing outputs. Each heating output operates accord-
ing to its start and stop temperature. Refer to sec-
tion 4.5 to enable heating outputs.
Reference Temperature:
Start/stop temperatures are related to the set point.
This means that they are automatically adjusted
when the set point changes.
Heaters 1-4
:
The controller has 4 basic heating outputs.
Heaters’ Hi Fire:
In addition to its 4 basic heating
outputs, the controller can simulate additional heat-
ing outputs with the Hi Fire option. When this op-
tion is used, the controller doubles the number of
heating outputs in use. Each simulated heating out-
put (Hi Fire Step) operates as a regular heating out-
put, with its own start/stop temperatures, relay
selection and probe selection. Refer to section 4.5
to activate the heaters’ Hi fire option.
Settings
Select:
Main menu
Start/Stop*
Heaters
* A password may be required to access this menu.
•
Set the following parameters:
On temperature
Set the temperature below which each heat-
ing stage starts. If the Hi/Lo fire option is
used, set this temperature separately for
both steps of the heating stage.
Off temperature
Set the temperature at which each heating
stage stops. Note that the
Off Temperature
of an heating stage must be at least 0.5°F
(0.3°C) higher that its
On Temperature.
If
the Hi/Lo fire option is used, set this tem-
perature separately for both steps of the
heating stage.
Main menu
Start/Stop
Heaters
Heaters Start / Stop
Use to navigate
Heater 2
Lo fire
On 71.0 °F
Off 73.0 °F
Hi fire
On 70.0 °F
Off 73.0 °F
Heater 1
Lo fire
On 73.0 °F
Off 75.0 °F
Hi fire
On 72.0 °F
Off 75.0 °F
Heat 1
Hi Fire On
Temperature
of the heater’s
probes
Heating
output
Heat 1
Hi Fire Off
Heat 1
Lo Fire On
Heat 1
Lo Fire Off
Heat 1
Hi Fire
Start T°
Heat 1
Hi Fire
Stop T°
Heat 1
Lo Fire
Start T°
Heat 1
Lo Fire
Stop T°
Operating Diagram
of an Heating Stage
31
EXPERT LA rev.00
EXPERT LA
4.12 Version
This menu shows the version number of your con-
troller program. This piece of information is useful
to get technical support.
Select:
Main menu
Setup*
User
Version
*
A password may be required to access this menu (sec. 4.2).
Main menu
Setup
User
Version
EXPERT LA
SOFTWARE
VX.X
4.11 Test Mode
The test mode is used to simulate temperature
changes and to verify the controller’s performances.
When the test is enabled, all outputs of the con-
troller operate according to the simulated tempera-
ture.
Select:
Main menu
Setup*
Test Mode
*
A password may be required to access this menu (sec. 4.2).
•
First, set the simulated temperature to the
desired value then set the test mode status
to “On” to start the test.
The test automatically ends after
15 minutes of inactivity. It can also
end sooner by switching the test mode
status back to “Off”.
Main menu
Setup
Test mode
Test mode
Use to navigate
Test Mode
Off
Temperature
72.3 °F