TEMPERATURE &
PRESSURE SETTINGS
5.1
Temperature Set Point
The temperature set point is a target temperature
in the room. The activation of most outputs of the
controller is based on this reference temperature.
Select:
Main menu
Set Points
Temp.
•
The following parameters are displayed:
Temperature set points are common
to all programs of the controller.
Current set point
This is the current temperature set point in
use. This value cannot be changed; to modify
the set point, change the day or night set
points below.
Day set point
Set the temperature set point that is used
during the day (this set point is used all day
long if the night set point is not enabled).
The controller can also change the day set
point automatically over time by using a
curve (see section 5.3).
This parameter can only be modified while the set
point curve is inactive (sec. 5.3).
Night set point
A different temperature set point can be
used at night. The night set point can be used
to lower the target room temperature for
instance. The night set point is relative to
the day set point, which means that it is
automatically adjusted when the day set
point changes. Set the night set point to the
desired value.
Accessible if the night set point is enabled (see
section 4.9)
Clean mode set point
Select what is the target room temperature
while the controller operates in clean mode.
Outside set point
The controller can adjust the moving speed
of natural ventilation curtains as a function
of outside temperature. When this function
is used, the controller refers to the outside
temperature set point to control the moving
speed. Set the outside temperature to the
desired value.
Accessible if the outside temperature sensor is en-
abled in section 4.7.1 and if the curtain compen-
sation is enabled in the Installation Setup (sec. 4.5).
Main menu
Set Points
Temp.
Set Points
Use to navigate
Set Points
Current
75.5 °F
Day
70.0 °F
Night
75.5 °F
Clean Mode
35.0 °F
Outside
75.0 °F
Curve Offset
0.0 °F
61
EXPERT LA rev.00
EXPERT LA
Settings
Select:
Main menu
Start/Stop*
Misting **
*
A password may be required to access this menu.
** Accessible if the misting output is enabled in the Installation
Setup (section 4.5).
•
Set the following parameters:
On temperature
Select the temperature at which the mist-
ing output starts.
Off temperature
Select the temperature below which the
misting output stops.
Minimum On & Off times
Set the on & off times of the minimum
misting timer.
Maximum temperature
Set the temperature at which the maximum
misting timer if used.
Maximum On & Off times
Set the on & off times of the maximum
misting timer.
Start & stop at
Specify the time range during which the
misting output can run.
Main menu
Start/Stop
Misting
Misting Settings
Use to navigate
On Temperature
85.0 °F
Off Temperature
83.0 °F
Minimum On Time
15 sec
Minimum Off Time
900 sec
Maximum Temperature
87.0 °F
Maximum On Time
180 sec
Maximum Off Time
900 sec
Start at
6:00A h:m
Stop at
9:00P h:m