56
EXPERT LA rev.00
EXPERT LA
6.5.2.2 Static-Pressure-Based Vent Door (Inlet)
Settings
Select:
Main menu
Vent/Inlet*
Vent door / Inlet 1 is already displayed; press
Vent door / Inlet 2 to display parameter set-
tings of the second inlet.
*
Accessible if at least one vent door (inlet) output enabled in
the Installation Setup (section 4.5). A password may also
be required to access this menu (section 4.2).
Make sure you have selected a static-
pressure-based vent door (inlet). Refer
to section 4.5 to set vent door (inlet)
functions.
•
Set the following parameters:
(Refer to the previous section to get further infor-
mation on these parameters).
Wind Effect Delay
Select what delay must elapse before mov-
ing the vent door (inlet) when the pressure
level exceeds a pressure set point.
Pre-opening Delay
Set the time that is required to pre-open the
vent door (inlet) before activating minimum
ventilation fans. Adjustable from 0 to 30 sec-
onds.
Main menu
Vent/Inlet
Vent Door/
Inlet 2
Auto Reset
Vent Door /Inlet 1 Settings
Use to navigate
Wind Effect Delay
0:30 m:s
PreOpening
15 sec
37
EXPERT LA rev.00
EXPERT LA
Main menu
Min. Vent.
MinV Relay
Vent Curve
Minimum Ventilation
Use to navigate
Min Vent. Status
On
Minimum Ventilation Timer
On time
15 sec
Cycle time
120 sec
6.
VENTILATION & COOLING
6.1
Minimum Ventilation
6.1.1
Minimum Ventilation Cycles
Definition
Minimum ventilation cycles are activated when the
average room temperature is below the start tem-
perature of fan stage 1. Running the fans even
though ventilation is not required for reducing the
room temperature is useful to reduce humidity lev-
els and supply oxygen to the room. It also prevents
the fans from freezing in winter.
Minimum ventilation timer
The minimum ventilation timer is composed of an
“On Time” and of a “Cycle Time”. The fans stay on
during the “On Time” then stop until the end of the
cycle. This timer is common to all programs of the
controller.
Minimum ventilation fans
Minimum ventilation is ensured by a user-defined
selection of On/Off fans. Refer to section 4.8.2 to
select these fans.
Automatic adjustment of the min. ventilation rate
The controller can automatically increase minimum
ventilation rates over time by increasing the “On
Time” portion of minimum ventilation cycles. Re-
fer to section 6.1.3.
Minimum Ventilation Timer
ON
ON TIME
OFF
CYCLE
TIME
6.1.2
Minimum Ventilation Settings
Select:
Main menu
Min. Vent.
•
Set the following parameters:
Minimum ventilation status
Select “On” to use minimum ventilation
cycles; select “Off” to disable this function.
Minimum ventilation timer
Set the “On Time” and the “Cycle Time” of
the minimum ventilation timer. The “Cycle
Time” must last longer than the “On Time”.
This timer is common to all programs of the
controller.
This parameter can only be modified while the
minimum ventilation curve is inactive (sec. 6.1.4).