58
EXPERT LA rev.00
EXPERT LA
Settings
Select:
Main menu
Start/Stop*
0-10V**
*
A password may be required to access this menu.
** Accessible if a 0-10V inlet output is enabled in the Installa-
tion Setup (section 4.5).
•
Set the following parameters:
Mode
Set the operating mode of the 0-10V output:
select “Automatic” if you want the controller
to control the output according to specified
parameter settings below or select “Manual”
to specify the inlet opening manually.
Opening
This is the current opening of the air inlet.
This opening can be changed when the
manual mode is enabled above.
Closed
This is the position of the air inlet during the
Off Time portion of minimum ventilation
cycles. Set this position to the desired value.
Stage #x
Assign an inlet opening (in %) to each fan
stage in use.
Over-Opening Settings:
Opening
Assign an inlet position to the over-
opening stage.
Bandwidth
Set the temperature range over which
the inlet gradually opens from the posi-
tion associated with the last fan stage
towards the over-opening position (see
graphic in section 6.6.1).
Main menu
Start/Stop
0-10V
0-10V #x
0-10V Inlet Settings
Use to navigate
Mode
Automatic
Opening
30 %
Closed
0 %
Stage 1
10 %
Stage 2
20 %
Stage 3
30 %
Over Opening settings
Opening
100 %
Bandwidth
5.0 °F
35
EXPERT LA rev.00
EXPERT LA
5.3.2
Curve Settings
Select:
Main menu
Set Points
SetP Curve*
*
Accessible if the temperature curve is enabled in the Instal-
lation setup (sec. 4.5). A password may also be required to
access this menu.
The following parameters can only be
modified while the curve is off.
If the curve is running, it is still possible
to adjust the value of all curve steps
simultaneously with the curve offset
parameter (see section 5.3.3).
•
Set the following parameters:
Current day
This is the current age of the animals. This
value may be changed to move backward
or forward on the curve. A change in the
current day also changes the animal age in
the “Age & mortality” menu.
Set point
The day set point is displayed.
Day numbers
Set the day at which each step starts. The
day number refers to the animal age. It is
adjustable from -5 to 450 days. Negative
values are used to prepare the house before
letting the animals enter.
Can only be modified while the curve is disabled.
Temperature set points
Assign a temperature set point to each step
of the curve.
Can only be modified while the curve is disabled
or by using the curve offset function (sec. 5.3.3).
Status
Select “On” to activate the curve. Once the
curve is on, the controller automatically ad-
justs the set point between consecutive
points of the curve; for this reason, curve
steps cannot be modified while the curve is
running.
Main menu
Set Points
SetP Curve
Temperature Curve Program 1
Use to navigate
Cur. Day
0 day
Set Point
70.0 °F
day
1
78.0 °F
day
10
75.0 °F
day
15
70.0 °F
day
20
65.0 °F
day
25
63.0 °F
day
30
61.0 °F
day
35
60.0 °F
day
40
60.0 °F
day
45
60.0 °F
day
50
60.0 °F
Status
Off