6
EXPERT LA rev.00
EXPERT LA
1.
INTRODUCTION
1.1
Precautions
We strongly recommend installing
supplementary natural ventilation as
well as a backup thermostat on at least
one cooling stage (refer to the relay pan-
els’ wiring diagram to connect the ther-
mostat).
Although fuses at the input and outputs
of the controller protect its circuits in
case of an overload or overvoltage, we
recommend installing an additional pro-
tection device on the controller's sup-
ply circuit.
The room temperature where the con-
troller is located MUST ALWAYS RE-
MAIN BETWEEN 32°F AND 104°F
(0°C TO 40°C).
To avoid exposing the controller to
harmful gases or excessive humidity, it
is preferable to install it in a corridor.
DO NOT SPRAY WATER
ON THE CONTROLLER!
1.2
Symbols of the Manual
Caution. Read the following text care-
fully. It contains important pieces of
information which, if ignored, may
cause the controller to operate im-
properly.
Pay attention. The following text con-
tains very useful information.
Press the
Main Menu
push-button.
Press the proper menu selector.
87
EXPERT LA rev.00
EXPERT LA
History menus 73
Humidity see Relative humidity
I
Inlets
Static-pressure-based inlets
see Vent door/inlet (pressure-
based)
Timer-based inlets
see Vent door/inlet (timer-based)
Inlets (0-10V inlet output)
Activation 20
Principle of operation 57
Probe assignment 26
Settings 58
Inputs
Activation 24
List of available inputs 7
Installation setup 19–22
Installer password
see Password
L
Language selection 12
LCD screen
Backlight button 12
Contrast adjustment 12
Location 12
LEDs
LED display
Location 12
Unit selection 22
LED meaning 13
Lights
Activation 19
Operation & Settings 63–65
Using additionnal on/off lights 27
Liters 18
M
Main menu button 11
Marketed animals
History 73
Posting # of marketed animals 74
Measuring units 18
Memory card
Erasing the card 79
Transfer process 77
Menu selectors 11
Minimum ventilation
Activation 37
Principle of operation 37
Relay assignment 28
Settings 37
Minimum ventilation curves
Principle of operation 38
Settings 39
Misting output
Activation 21
Operation & settings 60–61
Relay assignment 27
RH compensation on the mist output
Activation 23
Principle of operation 67
Settings 68
Mortality
Entering new mortalities 74
History 73
Posting # of mortalities 74
Mounting instructions 10
N
Natural ventilation curtain
Outside T° compensation 46
Outside T° set point 32
Principle of operation 44
Probe assignment 26
Purge cycles 47
Settings 45
Shutoff fans
Principle of operation 46
Relay selection 27
Night
see Day/night
O
Outputs
Activation 19–22
List of available outputs 7
Number of outputs 21
Relay assignment 27
Outside RH
see Rel. Humidity (RH)
Outside T°
see Temperature
P
Parameter adjustment 12
Password
Default user level 22
Enable/disable the password 22
Entering/changing the password 14–15
Retreiving a lost password 15
Probe
Activation 24
Assignment 26
Calibration 25
Connection 10
Extension 10
Probe sets
Current probe set in use 72
Principle of operation 49
Probe assignment 26
Settings 50
Programs
Automatic program switch
Activation 21
Settings 16, 21
Copy/paste program settings 17
Current program in use 72
Enabling programs 21
Principle of operation 16
Program selection 16
Purge cycles
Activation 21
Operation & settings 47
R
Ramping (stage 1)
Activation 21
Principle of operation 41
Relative humidity (RH)
Inside RH sensor
Activation 24
Calibration 25
Current reading 72
History 73
Outside RH sensor
Activation 24
Calibration 25
Current reading 72
History 73
RH Compensation
Principle of operation 67
Settings 68
RH set point 68
Relays
Alarm relay 71
Relay assignment 27
Shutoff fan relays in natural ventilation
Principle of operation 46
Relay selection 27