26
EXPERT LA rev.00
EXPERT LA
4.7.3
Probe Assignment
Some outputs of the controller (heaters, 0-10V
output and curtains) operate according to the av-
erage temperature measured by chosen tempera-
ture probes. You must assign temperature probes
to each of these outputs.
Room Temperature Sensors
Most cooling outputs (misting output, tunnel fans,
etc.) operate according to the average tempera-
ture in the room. You must select what tempera-
ture probes are used to measure the room tem-
perature.
Main menu
Setup
Probe Assgn
Heater
Heater 1 Probe Assignment
1
2
3
4
5
---
---
---
---
---
6
7
8
---
---
---
Settings
This section explain how to select temperature
probes that are used to measure the room tempera-
ture and how to assign temperature probes that
are used to control/ monitor the following outputs:
• Heaters 1-4
• 0-10V output
• Natural ventilation curtains
A template is available at the end of
this manual to write down your selec-
tion of sensors.
Probe Set 2
In tunnel ventilation, some changes in airflow pat-
terns can distort the room temperature calculation.
For this reason, it is possible to make another se-
lection to measure the room temperature in tunnel
ventilation. The second probe set must be enabled
in the Installation Setup to use this function (see
section 4.5).
Select:
Main menu
Setup*
Probe Assignment
Select the desired output ** :
- Room;
- Probe Set 2;
- Heaters 1-4 ;
- Heaters 1-4 Hi fire (opt.) ;
- 0-10V output ;
- Natural ventilation curtain 1-2.
*
A password may be required to access this menu (sec. 4.2).
** Only outputs that are enabled in the Setup menu are dis-
played (sec. 4.5).
•
Assign the desired temperature probes to
the selected output: select
“
" " to assign a
probe or select
“- - -
“ for probes that are
not assigned to the output.
67
EXPERT LA rev.00
EXPERT LA
10.
RH COMPENSATION
The controller offers different way to compensate
for high/low relative humidity (RH) levels in the
room. All compensation functions are explained
below. To use them, you must enable each desired
compensation function in section 4.6.
•
High RH Compensation
with Heating Outputs:
When RH levels are too high, the controller
can activate heating outputs in timer mode.
As RH levels increase, the controller in-
creases the On Time portion of the heating
cycle to compensate for the change. The
maximum compensated heating On Time is
reached when RH levels are 10% above the
RH Set Point.
•
High RH compensation with
cool cells & misting outputs:
If RH levels are too high, the controller can
stop the misting output and/or cool cell out-
put. Theses outputs are disabled when RH
levels reach the respective RH shutoff limit
of each output.
•
Low RH compensation
with misting outputs:
To compensate for low RH levels, the con-
troller can activate the misting output in
timer mode. The misting output starts when
RH levels decrease below the
Low RH Set
Point
.
RH Comp. with
Heating Outputs
Maximum
On Time
RH (%)
RH Set Point
On Time of
the heaters’
Timer
Minimum
On Time
Off