68
EXPERT LA rev.00
EXPERT LA
Settings
Select:
Main menu
RH Comp*
*
Accessible if at least one RH compensation function is en-
abled in section 4.6. In addition, a password may be re-
quired to access this menu (section 4.2).
•
Set the following parameters:
(Refer to the previous page to get further informa-
tion on these parameters)
RH Set Point
This is the humidity level above which high
RH compensation functions start. Adjustable
from 20 to 99% of humidity (select “Off”
to disable all high RH comp. functions).
Heater compensation
The timer used by heating outputs is made of an
On Time and of a Cycle Time. Heating outputs run
during the On Time then stop until the end of the
Cycle Time. The On Time portion of this cycle in-
creases as RH levels increase.
Minimum & Maximum On Times
Set the minimum and maximum On Times
of the heating timer. The minimum On Time
starts being used when indoor humidity lev-
els reach the RH set point; the maximum On
Time is used when humidity levels are 10%
above the RH set point.
Accessible if RH compensation with heating out-
puts is enabled in section 4.6.
Cycle Time
Set the cycle time of the heating timer.
Accessible if RH compensation with heating out-
puts is enabled in section 4.6.
Misting outputs on low humidity levels
Accessible if RH comp. on Low RH levels
is enabled in section 4.6.
Low Set Point
Set the humidity level below which misting
units start running in timer mode or select
“Off” to disable this function.
On & Off Times
Set the On and Off Times of the misting timer.
Mist & Cool Cell Shutoff
Set the humidity level above which the misting
output and/or the cool cell output stops or select
“Off” to disable this function.
Accessible if the mist shutoff compensation and/or cool cell shutoff
option is enabled in sec. 4.6.
ON
ON TIME
OFF
CYCLE
TIME
Main menu
RH Compens
RH Compensation
Use to navigate
RH Set Point
65 %
Heater Compensation
Min On Time
15 sec
Max On Time
45 sec
Cycle Time
300 sec
Mist on Low % Humidity
Low Set Point
Off %
On time
15 sec
Off Time
900 sec
Mist Shutoff
Off %
Cool Cell shutoff
Off %
25
EXPERT LA rev.00
EXPERT LA
4.7.2
Probe & Water Meter Calibration
You can slightly adjust the reading of each probe
input in order to obtain accurate and uniform read-
ings from all probes. In addition, if a water meter is
used, you must calibrate its water flow rate.
Select:
Main menu
Setup*
User
Prb Calib.
*
A password may be required to access this menu (sec. 4.2).
•
Adjust the reading of the probes (if required):
The probe calibration is common to all
programs of the controller.
Temperature probes (indoor & outdoor)
The reading of inside and outside tempera-
ture probes can be adjusted of ±3°F
(±1.7°C).
Relative humidity probe
The reading of inside and outside humidity
probes can be adjusted of ±3%.
Main menu
Setup
User
Prb calib
Probe Calibration
Use to navigate
Temperature Probe 1
0.0 °F
Temperature Probe 2
0.0 °F
Temperature Probe 3
0.0 °F
Temperature Probe 4
0.0 °F
Outside Probe 1
0.0 °F
Outside Probe 2
0.0 °F
Inside Humidity
0 %
Outside Humidity
0 %
Static Pressure
.000 ”WC
Water 1 Calibration
1 g/p
Water 2 Calibration
1 g/p
Water 3 Calibration
1 g/p
Static pressure probe
The reading of the static pressure probe can
be adjusted of±0.030"WC (±7Pa).
Water meter calibration
Specify the flow rate of each water meter.
It can be adjusted from 1 to 100 gallons (or
liters) per pulse.