4-11
Pager Programming Fields
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*160
Pager 1 Phone No.
Enter up to 20 digits
If you enter fewer than 20 digits, exit by pressing [
∗
] and next
field number. To clear entries from this field, press
∗
160
∗
.
*161
Pager 1 Characters
Enter up to 16 characters
Up to 16 optional characters may be sent as a prefix to the 7-
digit system status code sent to Pager #1 (if used). Phone
number in field *160 must have been entered. If fewer than
16 characters, exit by pressing [
∗
] and next field number. To
clear entries, press
∗
161
∗
.
For example, these optional 16 characters may be composed
of the following:
•
PIN number (to identify a specific pager to the paging
company)
•
Subscriber account number
•
∗
(enter # + 11 to send
∗
)
•
# (enter # + 12 to send #)
•
Pause (enter # + 13 to allow a 2-second pause)*
•
Any special character(s) the end user may decide to
transmit
* Some paging systems require pause(s) before the prefix.
Pager Format: XXX-YYYY where:
XXX
= 3-digit event code: 911 = Alarm
811 = Trouble
101 = Opening (disarm)
102 = Closing (arm AWAY)
YYYY = 4-digit user or zone number (depending on type of
event).
The first digit indicates partition (0 = system, 1 = part 1, 2 =
part 2, 3 = common), followed by the 3-digit user or zone
number.
Example 1.
Pager displays:
9 1 1 – 1 0 0 4
This indicates that the system is reporting an alarm (911)
caused by a fault in zone 4 (0004) in partition 1.
Example 2.
Pager displays:
1 0 2 – 2 0 0 5
This indicates that the system is reporting a closing–system
arming (102) by User 5 (0005) in partition 2.
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*162
Pager 1 Report Options
0 = No reports sent
1 = Open/close for all users enabled to
page†
4 = All alarms and troubles
5 = All alarms, troubles, and open/close
for all users enabled to page
12 = Alarms and troubles for zones
entered in zone list 9
13 = Alarms and troubles for zones
listed in zone list 9 and open/close
for all users enabled to page
Enter the types of reports to be sent to Pager 1 for each
partition.
† Reports to pager only when arming (close)/disarming (open)
from a touchpad using a security code; auto-
arming/disarming, arming with assigned button, and
keyswitch arming do not send pager messages.
*163
Pager 2 Phone No.
Enter up to 20 digits
If you enter fewer than 20 digits, exit by pressing [
∗
] and next
field number. To clear entries from this field, press
∗
163
∗
.
*164
Pager 2 Characters
Enter up to 16 characters
See field
∗
161 for explanation of entries. If fewer than 16
characters, exit by pressing [
∗
] and next field number. To
clear entries from this field, press
∗
164
∗
.
*165
Pager 2 Report Options
see pager 1 reports, field *162 for
entries, except use zone list 10.
Enter the types of reports to be sent to Pager 2 for each
partition.
Summary of Contents for Enterpreneur 3000EN
Page 64: ...3000EN Series Installation Instructions 6 6...
Page 68: ...3000EN Series Installation Instructions 8 2...
Page 78: ...3000EN Series Installation Instructions 12 2...
Page 82: ...13 4...
Page 88: ...3000EN Series Installation Instructions 14 6...
Page 92: ...3000EN SERIES INSTALLATION INSTRUCTIONS 15 4...
Page 96: ...3000EN SERIES INSTALLATION INSTRUCTIONS 17 2 NOTES...
Page 97: ...17 3 NOTES...
Page 98: ...3000EN SERIES INSTALLATION INSTRUCTIONS 17 4 NOTES...