3000EN Series: Installation Instructions
2-6
Backup Battery
1. Place the 12-volt backup battery in the cabinet.
2. After all connections to the control are completed, connect the red and black flying leads on the
control board to the battery. Do not attach these leads to the battery terminals until all
connections are completed.
Battery Saver Feature:
The battery will disconnect from the system after its voltage decreases
below 9VDC. This assists the control panel in recharging the battery when AC is restored.
Notes
IMPORTANT:
The panel will not power up initially on battery power only. You must plug the
transformer in first, and then connect the battery.
UL
For UL installations and Residential fire installations, refer to the chart below for the correct battery size
required to meet the mandatory standby time.
CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE
24-HOUR BATTERY BACKUP REQUIREMENTS
The California State Fire Marshal and UL have regulations which require that all residential fire alarm control
panels must be provided with a backup battery which has sufficient capacity to operate the panel and its attached
peripheral devices for 24 hours in the intended standby condition, followed by at least 4 minutes in the intended
fire alarm signaling condition. This control panel can meet these requirements without using a supplementary
power supply, provided that the panel’s auxiliary power and bell output currents are limited as indicated below.
OUTPUT LIMITATIONS TO MEET CSFM 24 HOUR BATTERY BACKUP REQUIREMENTS
AND UL RESIDENTIAL FIRE INSTALLATIONS
OUTPUT CURRENT LIMITATIONS
BATTERY INFORMATION
Output Current Total
Maximum Auxiliary Current
Battery Capacity
To Use (Amp/Hrs)
Recommended Battery
(Yuasa Model No.)
600mA maximum total of
auxiliary power plus bell
output currents
45mA
160mA
200mA
425mA
500mA
4AH
7AH
8AH
14AH
17.2AH
NP4-12 (or ADEMCO 467)
NP7-12
NP4-12 (two) ‡
NP7-12 (two) ‡
NPG18-12
‡
NOTE:
Use two batteries, connected in parallel. Use Ademco Battery Harness Kit SA5140-1. (Both batteries fit inside the cabinet.)
Earth Ground
Metal Cold Water Pipe:
Use a non-corrosive metal strap (copper is recommended) firmly secured to the pipe to which the
ground lead is electrically connected and secured.
AC Power Outlet Ground:
Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground terminal, use
a 3-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61-035, or
equivalent, available at most electrical supply stores.
Notes
•
This product has been designed and laboratory-tested to ensure its resistance to damage from
generally expected levels of lightning and electrical discharge, and does not normally require an
earth ground.
•
If an earth ground is desired for additional protection in areas of severe electrical activity, terminal
25 on the control board, or the cabinet, may be used as the ground connection point. The examples
of good earth grounds listed at the left are available at most installations.
Summary of Contents for Enterpreneur 3000EN
Page 64: ...3000EN Series Installation Instructions 6 6...
Page 68: ...3000EN Series Installation Instructions 8 2...
Page 78: ...3000EN Series Installation Instructions 12 2...
Page 82: ...13 4...
Page 88: ...3000EN Series Installation Instructions 14 6...
Page 92: ...3000EN SERIES INSTALLATION INSTRUCTIONS 15 4...
Page 96: ...3000EN SERIES INSTALLATION INSTRUCTIONS 17 2 NOTES...
Page 97: ...17 3 NOTES...
Page 98: ...3000EN SERIES INSTALLATION INSTRUCTIONS 17 4 NOTES...