3000EN Series: Installation Instructions
6-2
Start Output Device Mapping by pressing *79 while in Data Programming Mode. The following
prompts are displayed:
∗∗∗∗
79 Menu Mode
PROMPT
VALID ENTRIES
EXPLANATION
ENTER OUTPUT NO.
00 = QUIT
xx
Device Output Number
01-16, 17, 18
[
∗
] to continue
This is the logical (or reference) relay number as used in the
system. Relays and X-10 devices are numbered 01-16; the on-
board triggers are numbered 17 and 18 and can be
programmed for inverted output.
17 OUT NORM LOW
0 = NO 1 = YES
0
Output Normally Low
0 = no (standard default)
1 = yes
[
∗
] to continue
This prompt appears only for Triggers 17 and 18.
Selecting 0 (no) sets the output level normally high.
Selecting 1 (yes) sets the output normally low.
Output Trigger 17 can be used for resetting 4-wire smoke
detectors by connecting it to the negative power terminal of
the smoke detector, selecting 1 at this prompt, and setting as
zone type 54, fire zone reset, in *80 Menu mode.
After entry, display returns to Output Number prompt. Use
*80 Menu mode to program the function of the trigger.
XX OUTPUT TYPE
DELETE 0
Output Type
0 = delete
1 = relay on 4204/4229
module
2 = Powerline Carrier device
[
∗
] to continue
Select whether this is a relay or a Powerline Carrier (X-10)
device.
If relay is selected, skip to “B” prompt.
If Powerline Carrier device is selected, go to “A” prompt.
“A”
XX UNIT No.
yy
Unit Number
01-16 = predefined address
[
∗
] to continue
If X-10 is selected, a prompt for the unit number appears.
Enter the unit code (set at the device) and press [
∗
].
The system returns to the Output Number prompt.
“B”
XX MODULE ADDR
07-15 yy
Module Address
07-15 = predefined address
[
∗
] to continue
If relay is selected, this prompt appears.
Enter the predefined address for this module as listed below.
Make sure the module’s DIP switches are set to the selected
address.
Module Addresses
Address Module
07
1st 4229 (with zones 09-16)
08
2nd 4229 (with zones 17-24)
09
3rd 4229 (with zones 25-32)
10
4th 4229 (with zones 33-40)
11
5th 4229 (with zones 41-48)
12
1st
4204
13
2nd
4204
14
3rd
4204
15
4th
4204
XX REL POSITION
1-4 zz
Relay Position
1-4 = relay position
[
∗
] to continue
This is the actual (or physical) relay number with respect to
the Relay Module upon which it is located. For 4204 modules,
relay numbers are 1-4. For 4229 modules, relay numbers are
1-2.
The system returns to the Output Number prompt for
programming the next device.
Summary of Contents for Enterpreneur 3000EN
Page 64: ...3000EN Series Installation Instructions 6 6...
Page 68: ...3000EN Series Installation Instructions 8 2...
Page 78: ...3000EN Series Installation Instructions 12 2...
Page 82: ...13 4...
Page 88: ...3000EN Series Installation Instructions 14 6...
Page 92: ...3000EN SERIES INSTALLATION INSTRUCTIONS 15 4...
Page 96: ...3000EN SERIES INSTALLATION INSTRUCTIONS 17 2 NOTES...
Page 97: ...17 3 NOTES...
Page 98: ...3000EN SERIES INSTALLATION INSTRUCTIONS 17 4 NOTES...