background image

3000EN Series: Installation Instructions

 

 

 

5-8 

 

 

 

 

XMIT TO CONFIRM 

PRESS 

 TO SKIP 

 

Confirm

 

[

] to continue

 

13.  If “Yes” was entered at the 

SET TO CONFIRM?

 prompt 

previously (see first prompt following entry into the 

58 

Expert Programming Mode), the display on the left will 
appear. Confirm serial and loop numbers by activating 
the wireless key. 

 

IMPORTANT: 

When confirmed, the key is not active for arming/disarming 
until it is assigned to a user number (using the assigning 
attributes command, attribute “4”). See 

System Operation 

s

ection for procedure. 

 

 

 

Entd   A022-4063 

Rcvd  A022-4064 

 

Not Confirmed

 

[

] to continue

 

If the serial number transmitted does not match the serial 
number entered, a display similar to the one shown will 
appear. If the loop number does not match, it will also be 
displayed. 
If so,

 

activate the button on the wireless key once again. If a 

match is not obtained (i.e., summary display does not appear), 
press the [#] key and then enter the correct serial number. 

If the serial number transmitted matches the serial number 
entered, the touchpad will beep 3 times and will return you to 
step 8 (Zone Number prompt) to enter the starting zone for 
the next wireless key. Or you can return to *58 Menu mode by 
pressing 00 at the Zone Number prompt. 

 

NOTE:

 Following  the successful enrollment of each wireless 

device, remove 

ONE

 of the serial number labels from the 

device and affix it in the appropriate column on the 
ENROLLED TRANSMITTERS worksheet of the 
Programming Form; then enter the other information (zone 
number, zone type, loop number, etc.) relevant to that device. 

 

Wireless Key Predefined Default Templates 

YOU MUST

PROGRAM

THIS BUTTON

LOOP 4

LOOP 3

ENROLL AS "BR"

LOOP 1

LOOP 2

ON

OFF

5 8 0 4 - 0 0 1 - V 1

 

 

5804 Wireless Key Transmitter

 

 
 
 

Note: 

These transmitters 
are not intended for 
use in UL 
installations.

 

LOOP 3

LOOP 1

LOOP 2

LOOP 4
(YOU MUST
PROGRAM
THIS BUTTON)

RED/YELLOW

LED

••

• •

•••

GREEN/YELLOW

LED

ENROLL AS "BR"

5 8 0 4 B D - 0 0 7 - V 0

 

 

5804BD 2-Way Wireless Key Transmitter 

 

 

For 5804  

 

 

For 5804BD 

TEMPLATE 1 

Loop Function 

Zone 

Type 

TEMPLATE 4

 Loop 

Function 

Zone 

Type 

 

No Response 

23 

 

No Response 

23 

 2 

Disarm 

22 

 

No 

Response 

23 

 

Arm Away 

21 

 

Arm Away 

21 

 4 

No 

Response 

23 

 

Disarm 

22 

TEMPLATE 2

 Loop 

Function 

Zone 

Type 

TEMPLATE 5

 Loop 

Function 

Zone 

Type 

 

No Response 

23 

   

No Response 

23 

 2 

Disarm 

22 

 

 

Arm 

Stay 

20 

 

Arm Away 

21 

   

Arm Away 

21 

 4 

Arm 

Stay 

20 

 

 

Disarm 

22 

TEMPLATE 3

 Loop 

Function 

Zone 

Type 

TEMPLATE 6

 Loop 

Function 

Zone 

Type 

(same as temp. 2) 

No Response 

23 

(same as temp. 5) 

No Response 

23 

 2 

Disarm 

22 

 

 

Arm 

Stay 

20 

 

Arm Away 

21 

   

Arm Away 

21 

 4 

Arm 

Stay 

20 

 

 

Disarm 

22 

NOTE:

 Templates 3 and 6, which are identical to templates 2 and 5 respectively, are shown for future reference.  

Summary of Contents for Enterpreneur 3000EN

Page 1: ...ecurity Systems Security Systems Security Systems Installation and Set Up Guide ARMED READY 1 2 3 4 5 6 7 8 9 0 STAY BYPASS CHIME INSTANT AWAY CODE TEST OFF READY ARMED READY 1 2 3 4 5 6 7 8 9 0 STAY...

Page 2: ...n the hallway outside may not wake up the sleeper if the door is closed DINING KITCHEN BEDROOM BEDROOM BEDROOM BEDROOM LIVING ROOM BEDROOM BDRM DINING LIVING ROOM TV ROOM KITCHEN BEDROOM BEDROOM TO BR...

Page 3: ...3 1 About Programming 3 1 Zones and Partitions 3 1 Touchpads 3 2 Wireless Receiver Transmitters and Wireless Keys keyfobs 3 2 Pager Programming 3 2 Function Keys 3 3 Output Devices 3 3 Zone Type Defin...

Page 4: ...ble and Quick Program Commands 12 1 AVS Command Procedure 12 1 Quick Program Command Results 12 1 System Communication 13 1 Report Code Format Ademco Contact ID 13 1 Uploading Downloading via the Inte...

Page 5: ...ite maintenance independent of central station monitoring and modification to sites globally via the Internet UL NOTE Uploading Downloading via the Internet has not been evaluated by UL Functions Sing...

Page 6: ...acid type 12VDC 4AH minimum Long Range Radio Communication Device Primary telephone number messages can be reported via ECP connection to various communication devices check compatibility and availab...

Page 7: ...et can be closed and secured without a lock by using 2 screws in the cover s edge CABINET DOOR BOTTOM LOCKED UNLOCKED cab_lock_snap 001 V0 PUSH SNAP TAB SNAP TAB PUSH ON LOCK UNTIL IT IS SEATED SECURE...

Page 8: ...he cabinet into the blocks right hand terminals and tighten the screws Notes Do not mount the cabinet on or near metal objects This will decrease RF range and or block RF transmissions from wireless t...

Page 9: ...D RED WIRE TO TOUCHPAD GRN WIRE TO TOUCHPAD YEL WIRE pwr_supply 001 V0 Figure 4 Using a Supplementary Power Supply Notes Typical English Display 6150ADT Typical Custom English Display 6160ADT Typical...

Page 10: ...used Sounder Bell Connections 1 Make sounder connections to alarm output terminals 3 and 4 For supervised output continue with steps 2 and 3 2 Cut the red Bell Supervision Jumper located above termina...

Page 11: ...ns Notes Use caution when wiring the transformer to the control to guard against blowing the transformer fuse the fuse is non replaceable Wiring to the AC transformer must not exceed 250 feet using 16...

Page 12: ...panel s auxiliary power and bell output currents are limited as indicated below OUTPUT LIMITATIONS TO MEET CSFM 24 HOUR BATTERY BACKUP REQUIREMENTS AND UL RESIDENTIAL FIRE INSTALLATIONS OUTPUT CURREN...

Page 13: ...ansceiver 80mA 4219 Zone Expander 30mA 4204 Relay Unit 15 180mA 4229 Zone Expander Relay Unit 30 100mA 4286 Phone Module 300mA If using hardwire devices such as PIRs refer to the specifications for th...

Page 14: ...ector current draw 4 wire smoke detectors to any zone 2 8 as shown on the next page This control does not automatically reset power to 4 wire smoke detector zones so you must use a relay e g 4204 4229...

Page 15: ...PE 54 FIRE ZONE RESET 4 WIRE SMOKE OR COMBUSTION DETECTOR N C N O Figure 7a 4 Wire Smoke Detector Using Relay for Power Reset 2000 OHMS EOLR HEAT DETECTOR RED VIOLET AUX PWR 5 _ _ BLK _ 4_wiresmk 008...

Page 16: ...rol are 2000 ohms Expansion zones have normal response time 300 500 msec except zone connected to each module s loop A which can be set for fast response 10 15 msec 4219 4229 DIP Switch Address Settin...

Page 17: ...e received within 12 hours If the receiver is mounted remotely Place the RF receiver in a high centrally located area for best reception Do not locate the receiver or transmitters on or near metal obj...

Page 18: ...at the back of this manual Supervised transmitters send check in signals to the receiver at 70 90 minute intervals If at least one check in message is not received from each transmitter within a 12 h...

Page 19: ...gnals the keyswitch zone must be programmed to send opening and closing signals a UL commercial burglar alarm installation the keyswitch s tamper switch must be connected in to the alarm system This t...

Page 20: ...or if the module cover is removed and the tamper jumper is installed Alpha CHECK xx Wire Expansion FAULT xx Wire Expansion ALARM xx Wire Expansion Fixed Glass lxx or 91 if field 199 set for 2 digit di...

Page 21: ...NC DATA COM 1 3 4 5 6 7 8 KEY 12 AUX DATA COM SYNC GND OUT 17 RED OUT 18 GREEN ORANGE YELLOW BLUE PURPLE BLACK 00 trigcon 015 V0 8 PIN TRIGGER CONNECTOR Notes When using Powerline Carrier devices you...

Page 22: ...gers using 80 81 Menu modes as you would for any other relay output When using these outputs note pin 1 output number 17 trigger 1 15 ohms to ground when closed output low open when off output high no...

Page 23: ...e phone module to function even when accessing the system from an on premises phone If you are also using an Audio Alarm Verification AAV unit refer to Audio Alarm Verification AAV section for special...

Page 24: ...NE TIP RING PLUG DIRECT CONNECT CORD TIP RING GROUND TIP RING GREEN TIP RED RING INCOMING TELCO LINE GREY R BROWN T 4285 4286 TERMINAL ASSIGNMENTS 1 TIP 2 RING PHONE INPUT 3 TIP 4 RING PHONE OUTPUT 5...

Page 25: ...6 7 and program the zone as zone type 81 56 Menu mode E g Using output 18 for the trigger program an output function in 80 Menu mode as ZT 60 P 0 Action 1 Device 18 ON ON 1 2 3 4 5 6 7 8 1 2 3 4 5 6...

Page 26: ...CE TRIG GND 12VDC IN SWITCH BANK 2 SWITCH BANK 1 SWITCH BANK 2 SWITCH BANK 1 AUXILIARY AUDIO LEVEL ADJUSTMENT TRIM POT aav_uvcm 004 V1 ZONE TERMINALS OPTIONAL MONITORING ZONE CONNECTION USE ZONE TYPE...

Page 27: ...se unit board has several terminal blocks for making connections to remote stations telephone lines and to the control panel The AVS ADT base unit connects to the control s ECP terminals with all othe...

Page 28: ...HEADER RJ31X 1 2 3 4 5 6 7 8 RED BLK GRN YEL RED BLK GRN YEL RED BLK GRN YEL PANEL ECP PHONE AAV TO ALL OTHER ECP DEVICES LED VOLUME ID BUTTON LED NORMAL MODE PROGRAM MODE CALLBACK MODE PANEL TRIGGER...

Page 29: ...one Lists for relay powerline carrier zones chime night stay cross zone and pager zones 82 Alpha Programming Create alpha descriptors for easy zone identification 29 IP GSM Programming For programming...

Page 30: ...eless Key Programming Templates section of the 58 Expert Programming mode in Section 5 Zone Programming page 5 6 to program zone information and enroll each button of the wireless keys used Once a wir...

Page 31: ...provided when the panel is armed in the Instant mode Entry delay 1 is programmable for each partition Exit delay begins whenever the control is armed regardless of the arming mode selected and is ind...

Page 32: ...tion The check message will automatically disappear from the touchpad dynamically when the zone restores a user code off sequence is not needed to reset the zone Faults of this zone type are independe...

Page 33: ...e Custom English display touchpad Both partitions must be disarmed POWER UP NOTE firmware version display After powering up AC dI disabled or Busy Standby vx x Dl will be displayed after about 4 secon...

Page 34: ...onds of power up Table of Device Addresses This Device Uses Address Reports as Enabled By RF Receiver 00 100 56 zone programming input device type entry AUI 1 01 n a automatic if AUI enable field 189...

Page 35: ...must be 1 if wireless devices are used 23 Quick Forced Bypass 0 no quick forced bypass 1 allow quick bypass code 6 All zones bypassed by this function will be displayed after the bypass is initiated...

Page 36: ...med in field 33 1 no fire sounder timeout continue sounding until manually turned off This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances Temporal...

Page 37: ...the PABX entry and set call waiting disable option in field 91 to disable call waiting during control panel calls If the subscriber does not have call waiting and is not using PABX make no entry in th...

Page 38: ...xceed one minute use zone list 6 to disable dial delay from appropriate zones if necessary SIA Installations delay must be minimum of 15 seconds 53 Misc Fault Delay Time 0 15 secs 6 2 1 2 min 12 8 min...

Page 39: ...ng the UVS system or AVS system with non ECP connection option 0 must always be used If using the AVS system with ECP connection either option 0 or 1 may be used but note the following IMPORTANT If op...

Page 40: ...llations and required for residential fire alarm installations 63 Low Bat Report Code 0 no report 1st digit non zero send report Sent when a low battery condition exists in the system s battery UL Req...

Page 41: ...end report Sent after AC power has been restored after an AC power outage UL Required for UL commercial burglar alarm installations and required for residential fire alarm installations 74 Low Bat Res...

Page 42: ...nly after Exit Delay expires This option not for use in UL installations 86 Cancel Verify Touchpad Display 0 no 1 yes When enabled 1 yes this feature causes the message ALARM CANCELED to be displayed...

Page 43: ...call waiting cancel digits must be entered in field 40 PABX Code or Call Waiting Disable and the call waiting disable option must be enabled 1 in entry 2 When selected the system dials the entry in f...

Page 44: ...r should then call again The phone module will now seize the line and 2 long tones sound followed by the usual voice prompt for the access code If this procedure is not followed phone module operation...

Page 45: ...0 4 This indicates that the system is reporting an alarm 911 caused by a fault in zone 4 0004 in partition 1 Example 2 Pager displays 1 0 2 2 0 0 5 This indicates that the system is reporting a closi...

Page 46: ...ions 0 disable all options 1 RF Tamper reports during disarm 2 RF button types send low battery reports 8 RF low battery reports delayed 28 days E g Entering 10 8 2 enables button type transmitters to...

Page 47: ...e of the codes are suitable choose a code in the reserved range of 750 789 reserved for configurable zone type report codes and make sure to define the code with your central station 184 Configurable...

Page 48: ...s Display Selects how faults on zones set for this zone type are displayed Power Reset Verification Selects whether the system resets power when user enters code OFF and whether the system performs al...

Page 49: ...sarmed 3 never show any alarms trbles faults 0 no 4 power reset after fault with code OFF 12 verification see zone type 16 0 no 1 delay 1 2 delay 2 0 no 4 use exit delay 0 no 8 yes see note 2 Entry 7...

Page 50: ...es TOUCH SCREEN DEVICE NOTE If using more than one touch screen device with the system leave field 197 set to the default value 0 Touch Screen style touchpads automatically display remaining exit time...

Page 51: ...Programming mode by pressing 56 while in Data Programming mode The following prompts are displayed PROMPT VALID ENTRIES EXPLANATION SET TO CONFIRM 0 NO 1 YES Set to Confirm 0 no 1 yes If 1 Yes is ente...

Page 52: ...2 09 Fire 22 Disarm 03 Perimeter 10 Interior w Delay 23 No Alarm Resp 04 Interior Follower 12 Monitor Zone 24 Silent Burglary 05 Trouble Day Alarm Night 14 Carbon Monoxide 25 24 Hr Non Alarm 06 24 Hr...

Page 53: ...number Entry and Loop Number Entry see explanation to continue Used only when enrolling wireless transmitters a Transmit two open close sequences If using a button type transmitter press and release...

Page 54: ...e serial number will change to 0 s If 0 was entered in error simply re enter the loop number or press and the serial number will return to the display Zn ZT RC In L 10 03 10 RF 1s Summary Screen to co...

Page 55: ...D to go to prompts for wireless key programming templates A summary screen will appear showing zone 1 s currently programmed or default values Enter the zone number being programmed then press which d...

Page 56: ...the first prompt after entering 58 was answered Yes To confirm activate the loop input or button that corresponds to this zone The system checks for duplicate If a duplicate exists a long error beep w...

Page 57: ...PARTITION 1 Partition 1 partition 1 2 partition 2 to continue 6 Enter the partition in which the key is to be active 7 Press to continue ENTER START ZONE 00 QUIT 36 Start Zone Number to continue 8 Th...

Page 58: ...E Following the successful enrollment of each wireless device remove ONE of the serial number labels from the device and affix it in the appropriate column on the ENROLLED TRANSMITTERS worksheet of th...

Page 59: ...rt back to the last question to check or change an entry Press to go forward again Output Device programming involves 1 Use 79 Menu Mode to assign module and output numbers and map them to device addr...

Page 60: ...put Type 0 delete 1 relay on 4204 4229 module 2 Powerline Carrier device to continue Select whether this is a relay or a Powerline Carrier X 10 device If relay is selected skip to B prompt If Powerlin...

Page 61: ...ch defined function is associated with only one output number This means that if more than one output device needs to perform this particular function you need to define another output function number...

Page 62: ...umber See below for a list of available zone types CHOICES FOR ZONE TYPES 00 Not Used 05 Trouble Day Alarm Night 14 Carbon Monoxide 01 Ent Exit 1 06 24 Hr Silent 16 Fire w verification 02 Ent Exit 2 0...

Page 63: ...ut Action 0 6 see list at right Enter the desired device action as listed below Press the key to continue 0 off 4 Change Device State 1 Close for 2 seconds 5 Duration 1 see data field 177 2 Stay Close...

Page 64: ...3000EN Series Installation Instructions 6 6...

Page 65: ...l Delay Disable option Zone List 7 See field 93 for Unlimited Reports option Zone List Programming Zone List programming involves 1 Selecting an appropriate zone list number 2 Adding the desired zone...

Page 66: ...urns to the Zone List No prompt To delete a zone or zones in a zone list enter 1 to continue 01 Zn to Delete 00 Quit 00 Delete the Zone 01 64 zones to be deleted from list followed by to accept each z...

Page 67: ...partition to continue Enter the partition in which the function key is active Key A Func Zone 95 00 Define Key Function 00 12 see list to right to continue Returns to key number prompt with the next...

Page 68: ...3000EN Series Installation Instructions 8 2...

Page 69: ...se words shown in boldface type in the Alpha Vocabulary List The phone module will not provide annunciation of any other words Programming Zone Descriptors Menu Mode 82 Descriptor programming involves...

Page 70: ...Press 6 to accept the selected word and continue to the next word NOTE If this is the only word you are using for the descriptor press 8 instead of 6 to save that word in memory ZN 01 BACK D OOR Seco...

Page 71: ...st of letters numbers and symbols on a following page Press followed by the two digit entry for the first letter you would like to display e g 6 5 for A The cursor will then move to the right in posit...

Page 72: ...6 SENSOR 167 SERVICE 168 SHED 169 SHOCK 170 SHOP 171 SHORT 173 SIDE 174 SKYLIGHT 175 SLIDING 176 SMOKE 178 SONS 179 SOUTH 180 SPRINKLER 182 STATION 184 STORE 185 STORAGE 186 STORY 190 SUPERVISED 191 S...

Page 73: ...Disarm 07 Display Reminder 10 Display custom words 11 Periodic Test Report 12 Up and About to continue Enter the desired event number for event you want to occur at a specified time Events 10 12 are r...

Page 74: ...about REPEAT OPTION 0 4 X Repeat Option 0 do not repeat 1 repeat schedule weekly 2 repeat schedule biweekly every other week 3 repeat schedule every third week 4 repeat schedule every fourth week to c...

Page 75: ...ed key SHIFT functions Those functions shown in diagram above the numerical keys and the right hand functions shown on the ABC keys To perform a SHIFT key function press SHIFT key D key then press the...

Page 76: ...umber 2 B 2 For entering the number 2 B Used for entering C S ID number 3 C 3 For entering the number 3 C Used for entering C S ID number 4 D 4 For entering the number 4 D Used for entering C S ID num...

Page 77: ...installer code 0 5 remove all programming options set by 0 3 quick command installer code 0 6 remove all programming options set by 0 4 quick command Quick Program Command Results When either the 03...

Page 78: ...3000EN Series Installation Instructions 12 2...

Page 79: ...er or system status number see the following page Ademco Contact ID Reporting takes the following format CCCC CCCCCC Q EEE GG ZZZ where CCCC CCCCCC Customer subscriber ID 4 or 10 digits depending on f...

Page 80: ...larm 380 Global Trouble Trouble Day Night Canadian panels log and report this code Code Definition 381 RF Sensor Supervision 382 Supervision Auxiliary Wire Zone 383 RF Sensor Tamper 384 RF Sensor Low...

Page 81: ...allation Site Internet Intranet Communication Module 7720P Programmer Ethernet Network Connection IP compatible Control Panel At the Downloading Office 7810iR ent IP Receiver Internal Router Computer...

Page 82: ...13 4...

Page 83: ...can change system master code view event log set system clock program touchpad macro program scheduled events activate output devices triggers relays Partition Master default P1 03 P2 33 same as Mast...

Page 84: ...only 4 partition master 2 guest Access Group System Partition Master Code 8 user no 2 group 1 8 Factory Assignments none You can assign users to a group then set an access schedule that defines the t...

Page 85: ...ayed To clear this display simply repeat the disarm sequence enter the security code and press the OFF key again Arming Away Enter code AWAY 2 or simply press appropriate lettered key on the touchpads...

Page 86: ...cy Fire Emergency B 99 24 hour Audible 24 hour Audible C 96 24 hour Auxiliary IMPORTANT For a Silent panic function if programmed to be of practical value you must program a report code for the zone a...

Page 87: ...display may occur Some wireless sensors use a non replaceable long life battery which requires replacement of the entire unit at the end of battery life e g 5802 5802CP TELCO FAULT 94 Telephone Line F...

Page 88: ...3000EN Series Installation Instructions 14 6...

Page 89: ...windows with contacts should be closed PIRs should be covered use a cloth to mask them temporarily if necessary If a NOT READY message is displayed press to display the faulted zone s Restore faulted...

Page 90: ...ops zones Any transmitter that is not enrolled will not turn off its zone number Go No Go Test Mode The Go No Go Test verifies adequate RF signal strength from the proposed transmitter location and al...

Page 91: ...test report sent every 24 hours installer code 0 1 test report sent once per week installer code 0 2 test report sent every 28 days Each mode sets schedule 32 to the selected repeat option the first t...

Page 92: ...3000EN SERIES INSTALLATION INSTRUCTIONS 15 4...

Page 93: ...accepts up to 16 transmitters 5883H accepts up to system max transmitters 5800TM Transmitter Module used with 5827BD Wireless 2 Way Touchpad Zone Expansion 4219 WIRED EXPANSION MODULE 4229 WIRED EXPAN...

Page 94: ...AS RF LOOP 1 INTERNAL SHOCK SENSOR LOOP 2 REED 5819 ENROLL AS RF LOOP 2 REED LOOP 3 TERMINALS LOOP 1 TERMINALS 5800WAVE SET HOUSE ID ENROLL AS RF 5800Micra ENROLL AS RF 5800CO ENROLL AS RF 5801 ENROL...

Page 95: ...er should be aware that compliance with the above conditions may not prevent degradation of service in some situations Repairs to certified equipment should be coordinated by a representative designat...

Page 96: ...3000EN SERIES INSTALLATION INSTRUCTIONS 17 2 NOTES...

Page 97: ...17 3 NOTES...

Page 98: ...3000EN SERIES INSTALLATION INSTRUCTIONS 17 4 NOTES...

Page 99: ...rcuits children playing with matches or arson Depending on the nature of the fire and or location of the smoke detectors the detector even if it operates as anticipated may not provide sufficient warn...

Page 100: ...idity high or low temperatures as well as large swings in temperature may all reduce the actual battery life in a given installation This wireless system however can identify a true low battery situat...

Page 101: ...umber 4 16 Download Phone Number 4 9 Duplicating Wireless Keys 5 7 Dynamic Signaling Delay 4 4 Dynamic Signaling Priority 4 5 E Earth Ground 2 6 ECP Fail Display 4 16 Enrolling 2 12 5 1 Entering Seria...

Page 102: ...em Test 13 1 T Tamper Switch 2 13 Telco Line 2 17 Telephone Line Monitoring 1 1 Test Mode 13 1 Test Procedures 13 1 Test Report Code 4 6 Test Restore Report Code 4 7 Touchpad Addresses 2 3 Touchpad Fu...

Page 103: ...TO PHONE TERMINALS SEE INSTRUCTIONS REMOTE TOUCHPADS EACH PARTITION CAN USE 6150ADT OR 6160ADT TOUCHPADS SEE INSTRUCTIONS PROVIDED WITH TOUCHPAD LOCAL PROGRAMMING MUST BE DONE WITH A 6160ADT BUT NEED...

Page 104: ...ADT Security Services Inc One Town Center Rd Boca Raton FL 33486 Copyright 2003 K5305V8s K5305V8 11 10 Rev A SIA...

Reviews: