3000EN Series: Installation Instructions
5-2
PROMPT
VALID ENTRIES
EXPLANATION
Zn ZT P RC In: L
10 00 1 10 RF: 1
OR
Zn ZT P RC In: AD
10 00 1 10 AW: 07
OR
Zn ZT P RC HW: RT
10 00 1 10 EL 1
Summary Screen
[
∗
] to continue
A summary display appears.
“IN: L” appears for wireless zones and indicates input type
and loop.
“IN: AD” appears for hardwire expansion zones (AW) and
indicates the module’s address (AD), which is based on the
zone number.
“HW: RT” appears for hardwire zones and indicates
configuration (EOL, NO, NC ) and response time selection.
10 Zone Type
Perimeter 03
Zone Type (ZT)
(see table at right; types
92/93 only programmable
via downloader)
Each zone must be assigned to a zone type, which defines the
way in which the system responds to faults in that zone.
Enter the Zone Type code from the list below:
Note:
If 00 is entered,
Delete Zone ?
will be displayed.
00 = Not used
07 = 24-Hr Audible
20 = Arm–STAY*
01 = Entry/exit #1
08 = 24-Hr Aux
21 = Arm–AWAY*
02 = Entry/exit #2
09 = Fire
22 = Disarm*
03 = Perimeter
10 = Interior w/Delay 23 = No Alarm Resp
04 = Interior Follower
12 = Monitor Zone
24 = Silent Burglary
05 = Trouble Day/Alarm Night 14 = Carbon Monoxide 25 = 24-Hr Non-Alarm
06 = 24-Hr Silent
16 = Fire w/Verify
77 = Keyswitch
81 = AAV Monitor Zone
*5800 button-type transmitters only
90-93 = Configurable
10 Partition
1
Partition No. (P)
1-3 = partition (3 = common)
[
∗
] to continue
Enter the Partition number for this zone. Partition 1 is shown
entered.
10 Report Code
1st 01 2nd 00 10
Report Code (RC)
First Digit:
01† = enable CID report
00 = disable CID report
Second Digit: entries
ignored
[
∗
] to continue
Entering any non-zero entry as the first digit enables the
Contact ID report code for this zone. Refer to the
System
Communication
section for information about report codes
and formats.
† typical entry
02 HARDWIRE TYPE
EOL 0
Hardwire Type
0 = EOL
1 = NC
2 = NO
[
∗
] to continue
This prompt appears only for zone numbers 02-08.
Zone 1 is automatically set for EOL operation.
02 Response Time
1
Response Time (RT)
0 = 10mSec
1 = 350mSec
2 = 700mSec
3 = 1.2 seconds
[
∗
] to continue
This prompt appears only for hard-wired zones 01-08 (zone 02
is used as an example in display).
Summary of Contents for Enterpreneur 3000EN
Page 64: ...3000EN Series Installation Instructions 6 6...
Page 68: ...3000EN Series Installation Instructions 8 2...
Page 78: ...3000EN Series Installation Instructions 12 2...
Page 82: ...13 4...
Page 88: ...3000EN Series Installation Instructions 14 6...
Page 92: ...3000EN SERIES INSTALLATION INSTRUCTIONS 15 4...
Page 96: ...3000EN SERIES INSTALLATION INSTRUCTIONS 17 2 NOTES...
Page 97: ...17 3 NOTES...
Page 98: ...3000EN SERIES INSTALLATION INSTRUCTIONS 17 4 NOTES...