3000EN Series: Installation Instructions
4-6
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*59
Exit Error Alarm Report Code
SIA NOTE: exit error report is always
enabled
The Contact ID message will contain
the zone number and error code 374
(“ALARM–EXIT ERROR”).
After arming the system, entry/exit and interior zones
remaining open after exit delay expires cause an alarm sound
at the touchpad and external sounder (touchpad also displays
“EXIT ALARM”), and entry delay begins. Disarming before
the end of the entry delay stops the alarm sounding and no
message is sent to the central station. The touchpad will
display “CA” (English displays) or “ALARM CANCELED”
(Custom displays).
If the system is not disarmed before entry delay expires, an
“EXIT ALARM” message and a zone alarm message is sent to
the central station. The touchpad will display “EA” (English
display ) or “EXIT ALARM” (Custom English display), and
alarm sounding continues until the system is disarmed (or
timeout occurs).
If a fault occurs in an exit or interior zone within 2 minutes
following the end of the exit delay, a “RECENT CLOSING”
message is sent to the central station. See field *69 Recent
Closing Report.
*60
Trouble Report Code
0 = no report
1st digit non-zero = send report
This will be sent if a zone has a trouble condition.
UL: Required for UL commercial burglar alarm installations
and required for residential fire alarm installations.
*61
Bypass Report Code
0 = no report
1st digit non-zero = send report
This will be sent when a zone is manually bypassed.
UL: Required for UL commercial burglar alarm installations.
*62
AC Loss Report Code
0 = no report
1st digit non-zero = send report
Timing of report is random with up to a 4-hour delay. If AC
restores before the report is sent, there is no “AC LOSS” report.
UL: Required for UL commercial burglar alarm installations
and required for residential fire alarm installations.
*63
Low Bat Report Code
0 = no report
1st digit non-zero = send report
Sent when a low-battery condition exists in the system’s battery.
UL: Required for UL commercial burglar alarm installations
and required for residential fire alarm installations.
*64
Test Report Code
0 = no report
1st digit non-zero = send report
Periodic Test Report Scheduling Commands:
installer code + [#] + [0] + 0 = report every
24 hrs
installer code + [#] + [0] + 1 = report once
per week
installer code + [#] + [0] + 2 = report every
28 days
Sent periodically to test that the communicator and phone lines
are operational.
UL: Required for UL commercial burglar alarm installations
and required for residential fire alarm installations.
Use Scheduling mode (event 11) or the key commands listed
below to set the frequency of periodic test reports. Each
command sets schedule 32 to the stated repeat option; first test
report sent 12 hours after command.
NOTE:
Make sure the Real-Time Clock is set to the proper
time
before
entering the test report schedule command to
ensure that test reports are sent when expected.
*65
Open Report Code
0 = no report
1st digit non-zero = send report
This is sent upon disarming of the system in the selected
partitions.
UL: Required for UL commercial burglar alarm installations.
*66
Arm Away/Stay Report Code
0 = no report
1st digit non-zero = send report
This option allows for independent programming of Away and
Stay reports for each partition, including the common lobby.
NOTE:
“OPEN” reports are not sent if the associated closing
report is not enabled.
*67
RF Trans. Low Batt. Report Code
0 = no report
1st digit non-zero = send report
Sent when a wireless transmitter low-battery condition exists.
UL installations: must be enabled if wireless devices are used;
Required for UL commercial burglar alarm installations.
*68
Cancel Report Code
0 = no report
1st digit non-zero = send report
This is sent upon disarming of the system after an alarm
condition was reported.
SIA NOTE: Report enabled.
Summary of Contents for Enterpreneur 3000EN
Page 64: ...3000EN Series Installation Instructions 6 6...
Page 68: ...3000EN Series Installation Instructions 8 2...
Page 78: ...3000EN Series Installation Instructions 12 2...
Page 82: ...13 4...
Page 88: ...3000EN Series Installation Instructions 14 6...
Page 92: ...3000EN SERIES INSTALLATION INSTRUCTIONS 15 4...
Page 96: ...3000EN SERIES INSTALLATION INSTRUCTIONS 17 2 NOTES...
Page 97: ...17 3 NOTES...
Page 98: ...3000EN SERIES INSTALLATION INSTRUCTIONS 17 4 NOTES...