4-7
*69
Recent Closing Report Code
SIA NOTE: Recent closing report is
always enabled.
The Contact ID message will contain
the zone number and error code 459
(“RECENT CLOSING”).
Similar to the Exit Error condition described in field *59, but
occurs if any burglary zone is faulted within two minutes
after
the initial exit delay expires. Disarming the system within the
two minutes stops the alarm sound and displays " ALARM
CANCELED " or "CA" and the faulted zone number. No
message is sent to the Central Monitoring Station.
If the system is not disarmed within two minutes, the alarm
sound continues and a “recent closing” and a “zone alarm”
message are sent to the Central Monitoring Station (after dial
delay expires).
Restore Report Codes (
∗∗∗∗
70–
∗∗∗∗
76)
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*70
Alarm Restore Report Code
0 = no report
non-zero = send report
Sent when an alarm zone is restored to non-faulted condition.
UL: Required for UL commercial burglar alarm installations
and required for residential fire alarm installations.
*71
Trouble Restore Report Code
0 = no report
1st digit non-zero = send report
This is sent when a trouble in a zone is restored and code +
OFF performed.
UL: Required for residential fire alarm installations.
*72
Bypass Restore Report Code
0 = no report
1st digit non-zero = send report
This is sent when a zone that has been bypassed is
unbypassed.
UL: Required for UL commercial burglar alarm installations.
*73
AC Restore Report Code
0 = no report
1st digit non-zero = send report
Sent after AC power has been restored after an AC power
outage.
UL: Required for UL commercial burglar alarm installations
and required for residential fire alarm installations.
*74
Low Bat Restore Report Code
0 = no report
1st digit non-zero = send report
Sent after a system low-battery condition is restored to normal.
UL: Required for UL commercial burglar alarm installations
and required for residential fire alarm installations.
*75
RF Xmtr Low Batt. Restore Code
0 = no report
1st digit non-zero = send report
Sent when a transmitter’s low battery condition is restored
(i.e., new battery installed).
UL installations: must be enabled if wireless devices are used;
Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*76
Test Restore Report Code
0 = no report
1st digit non-zero = send report
This is sent when the Test mode is exited or upon timeout
(4hrs).
UL: Required for UL commercial burglar alarm installations
and required for residential fire alarm installations.
Miscellaneous System Fields
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*77
Daylight Saving Time
Start/End Month
0 = Disabled
4 = April
1 = Jan
# + 10 = Oct
2 = Feb
# + 11 = Nov
3 = Mar
# + 12 = Dec
Enter the start and end month for daylight savings time, if
applicable to the region.
*78
Daylight Saving Time
Start/End Weekend
0 = disabled
4 = fourth
1 = first
5 = last
2 = second
6 = next to last
3 = third
7 = third to last
Enter the start and end weekend for daylight savings time, if
applicable to the region.
*79
Output Device Mapping Menu
Mode
Use this menu mode to enter output devices/powerline carrier
devices into the system. See Output Device Programming section
for procedures.
Summary of Contents for Enterpreneur 3000EN
Page 64: ...3000EN Series Installation Instructions 6 6...
Page 68: ...3000EN Series Installation Instructions 8 2...
Page 78: ...3000EN Series Installation Instructions 12 2...
Page 82: ...13 4...
Page 88: ...3000EN Series Installation Instructions 14 6...
Page 92: ...3000EN SERIES INSTALLATION INSTRUCTIONS 15 4...
Page 96: ...3000EN SERIES INSTALLATION INSTRUCTIONS 17 2 NOTES...
Page 97: ...17 3 NOTES...
Page 98: ...3000EN SERIES INSTALLATION INSTRUCTIONS 17 4 NOTES...