1-1
S E C T I O N 1
General Description
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
In This Section
♦
About the FOCUS 200 PLUS System
♦
Prominent Features
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
About the FOCUS 200 PLUS System
The FOCUS 200 PLUS is a UL Listed commercial burglar and fire alarm system that provides:
•
A control unit circuit board that contains:
•
Dual microprocessor firmware IC chips (16-bit primary MPU, 8-bit secondary).
•
A non-volatile SRAM IC chip for storing the programmed data, so the data will not be lost if
the system loses all power.
•
Control of the system via user-friendly operating panels. The operating panel provides:
•
Four lines of interactive messages.
•
Menus to guide the user through simple selection processes.
•
Up to 255 points of protection that are divided among input and output points.
•
Up to 8 BA groups.
•
2 built-in supervised bell outputs for compliance with local FA requirements, as well as for use
with BA applications.
•
A built-in communicator and supports an optional backup dialer or an optional AC communicator
module for monitoring purposes to a Customer Care Center.
•
Up to 255 users, of which the first 99 may use ID codes and/or card/keys to access the system. The
remaining are card/key users only.
•
The ability to downline load the programming from a remote location using the Service Terminal
Downloader.
•
Default data parameters stored in a read-only memory (ROM). This default data may be
transferred from the ROM to the SRAM by issuing a command at an operating panel.
Prominent Features
Below is a list of the prominent features of the system. For a detailed explanation of any of the
features, see the appropriate section.
•
Eight built-in points, including two 2-wire smoke detector loops.
•
Built-in programmable style "D" fire loop.
•
Capability of employing up to 16 operating panels for a given system, with a single operating panel
controlling all BA groups.
•
Freedom of customer to determine names that will appear on operating panel displays for each
point of protection, each BA group, and each ID code.
•
Two RS-485 buses employed for communicating with and powering the gateways, operating panels,
printer interface units, and sensors via gateways.
•
Up to eight gateways (SIM, PID, and RF) that serve as interfaces for sensors and output devices.
Summary of Contents for Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Page 2: ......
Page 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Page 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Page 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Page 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Page 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Page 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Page 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Page 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Page 210: ...Index Index 6...
Page 214: ...A 4...