FOCUS 200 PLUS Installation and Setup Guide
6-4
Description
Function
Access
Control BA1
Used for controlling access to BA1 by having an output operate a door strike. The
output is normally released. It operates for 10 seconds when a valid ID code is
entered at the operating panel if BA group is off or when BA group is turned off.
Operating panel must be assigned to Unit Number 0.
Access
Control BA2
Same function as Access Control BA1 except it relates to BA2. Operating panel
must be assigned to Unit Number 1.
Access
Control BA3
Same function as Access Control BA1 except it relates to BA3. Operating panel
must be assigned to Unit Number 2.
Access
Control BA4
Same function as Access Control BA1 except it relates to BA4. Operating panel
must be assigned to Unit Number 3.
Access
Control BA5
Same function as Access Control BA1 except it relates to BA5. Operating panel
must be assigned to Unit Number 4.
Access
Control BA6
Same function as Access Control BA1 except it relates to BA6. Operating panel
must be assigned to Unit Number 5.
Access
Control BA7
Same function as Access Control BA1 except it relates to BA7. Operating panel
must be assigned to Unit Number 6.
Access
Control BA8
Same function as Access Control BA1 except it relates to BA8. Operating panel
must be assigned to Unit Number 7.
For the above Access Control functions the controlling operating panel must be located outside of the
entry door for the associated BA group. For information about installing and addressing, refer to the
Installing the Operating Panel and Access Control sections.
Description
Function
Telco
Backup
This is a separate option associated with each of the three outputs, and is intended
for systems that are connected to a CCC. It is used in conjunction with the selected
function for which the output is to operate. If this option is chosen, the output will
operate for the selected function only if there is a telco problem on the AC or FSK
dialer line, in which case the output can be used to trigger a direct-connect
transmitter to a Police Headquarters or other receiving station as a backup.
4-Wire
Smoke
Detector
Reset
This operates the output when fire alarms are reset during the Alarm Reset
sequence. The function requires the power to the 4-wire sensors to be wired via the
output. The output operates for approximately 6 seconds.
Light
Output turns on when the protection of a pre-selected BA group is turned off, or the
entry/exit delay period is activated. The output turns off when the protection of a
BA group is turned on.
Note: If the Recycle Exit Delay is enabled, the output turns on whenever any key is
pressed on the operating panel.
Installing the External Sounders
Select compatible alarm-indicating devices from the list that follows. Be sure the total current drawn
on each output and the total combined with the auxiliary power outputs does not exceed the values
stated earlier in this section.
Bell Output Supervision
The bell outputs are automatically supervised whenever an output point type is programmed for points
246 and 247, bell 1 and bell 2, respectively. The system will trigger a trouble condition, regardless of
the On/Off status of the BA group(s), whenever a short or an open is detected on the bell output wiring.
To supervise the bell outputs:
1.
Install a 2k ohm resistor across the last notification appliance on each output.
2.
Program an SPV point type for points 246 and 247.
Summary of Contents for Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Page 2: ......
Page 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Page 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Page 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Page 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Page 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Page 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Page 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Page 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Page 210: ...Index Index 6...
Page 214: ...A 4...