FOCUS 200 PLUS Installation and Setup Guide
15-4
Guidelines for Programming Permanent and Temporary Schedules
•
If there isn't any opening or closing, program UUUU for both the opening and the closing.
•
If UUUU is programmed for the opening, then it must also be programmed for the closing.
•
If there is no opening time, but there is a closing time, the opening must be entered as 12 midnight
(12:00 AM). This will allow entering any closing time that is desired.
•
No permanent or temporary opening time can be assigned if it is before the earliest open time that
has been programmed for the BA group.
•
Changes can be made to the permanent and temporary schedules by someone with the appropriate
privilege levels.
Any permanent or temporary schedule can be downline loaded, regardless of the earliest-open or latest-
close time that has been programmed in the control unit.
Holiday Schedules
The holiday schedule:
•
Specifies each day during the year that the premises will be closed for the observance of a holiday.
•
Overrides the permanent schedule for that day.
•
Accommodates l4 days that are designated as holidays.
•
Requires the programming of the month, day of the month, and name of the holiday for each
holiday.
•
Can be overridden by a temporary schedule, if a BA group needs to be opened during the holiday.
If you are using a permanent schedule to perform Auto On/Off, then completing this schedule is
important, otherwise a false alarm may be generated. If an Auto Off function has been selected for any
BA group and the holiday falls on what would otherwise be a normal workday, the protection will not
be automatically turned off during the holiday at the normal opening time. When someone arrives at
the facility and enters, expecting the system to be Off, a false alarm will be generated.
Ambush Schedule
An ambush schedule:
•
Is used for an Ambush-Start point and an Ambush-End point as protection against hide-ins.
•
Provides for two permanent schedule openings and closings per day.
•
Provides for two temporary schedule openings and closings per day.
•
Is programmed in the same way as the permanent and temporary schedules for each BA group.
•
Operates independently of other schedules.
Open and close times for a given day should form a time window spanning the permanent schedule
open time to permit the customer to enter in order to prepare for the opening of the bank without
creating an alarm.
See the Ambush Start and End Input Point Types in the Input and Output Point Types section for an
explanation of how an ambush schedule works.
Summary of Contents for Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Page 2: ......
Page 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Page 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Page 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Page 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Page 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Page 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Page 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Page 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Page 210: ...Index Index 6...
Page 214: ...A 4...