Section 6 – Bell Outputs and Auxiliary Relay
6-7
Wiring the Auxiliary Relay
The auxiliary relay cannot be supervised. It is typically used for annunciating burglary alarms,
resetting 4-wire smoke detectors, elevator recall, or other situations that do not require the supervision
of the wiring. Be sure to set jumper P3 for either wet or dry operation.
Figure 6-2 shows how to wire the auxiliary relay to operate an unsupervised external alarm sounder.
Short pins 1 and 2 on P3 for wet operation for this application. See the Basic Hardwired Points section
for the wiring of the auxiliary relay for 4-wire smoke detector reset operation.
AUX. RELAY
9
10
11
P3
JUMPER P3
Pins 1 & 2 shorted = wet
Pins 2 & 3 shorted = dry
N.C
.
WET/DR
Y
N.O
.
12
GND
BELL
ALARM
Figure 6-2: External Sounder Connections to the Auxiliary Relay
Programming the Bell Outputs
Refer to Programming the Point Data in the Programming section for information about the procedure.
Bell output 1 and bell output 2 are points 246 and 247, respectively.
Defaults for the bell output points are:
Point
Description
Default Type
Gateway #
Hard ID
246
Bell 2
SPV
8
122
247
Bell 1
SPV
8
121
Summary of Contents for Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Page 2: ......
Page 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Page 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Page 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Page 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Page 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Page 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Page 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Page 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Page 210: ...Index Index 6...
Page 214: ...A 4...