Section 6 – Bell Outputs and Auxiliary Relay
6-3
Description
Function
Bell
Note: The output is reset by entering a valid ID code at any operating panel, unless
stated otherwise.
Note: Programmed bell timeout is 0 to 255 minutes in 1-minute increments unless
stated otherwise.
The output activates when triggered by the following occurrences:
•
Burglar Alarm: Alarm in any BA group will cause steady activation until valid
ID code is entered or bell timeout is reached. If the BA group has been
programmed for a delay in start of bell ringing, the start of the bell is delayed by
the programmed delay time (up to 20 minutes in 1-minute increments).
•
Fire Alarm: Bell rings for 10 minutes with the pattern 1-second-On/1-second-Off,
with a 5-second pause every 10 seconds until silenced by entering a valid ID
code, or until the 10 minutes expire. The bell can also be silenced using special
Fire Marshall Code (222222). (May also be set via option 3 for temporal pattern).
See the Input and Output Point Types section.
•
BA Keyswitch Point: Output activates bell (
∗
) for an open, tamper, or comm fail
condition during Nite Set of the BA group. Bell will continue to ring until valid
ID is entered or bell timeout is reached.
•
Remote Power Supply Point: Output activates bell (
∗
) for a tamper or comm fail
condition of remote power supply point. Bell will continue to ring until valid ID
is entered or bell timeout is reached.
•
System Self-Supervision: Output activates bell (
∗
) for a cabinet tamper during
Nite Set of BA1.
•
Janitor Keyswitch Point: Output activates bell for a tamper or comm fail
condition during Nite Set. Bell will continue to ring until valid ID is entered or
bell timeout is reached.
•
Bell On No Close: Output activates bell for 10 minutes if system has not been
closed at scheduled closing time. Bell ringing starts either 5 or 15 minutes after
scheduled closing time, depending on the choice made for the No Close option
(see the Scheduling section).
•
Display and Bell Test: This is a 30-second test that is initiated from an
operating panel (see the Testing the System section). Output activates bell for
the final 4 seconds of test.
•
Auto Bell Test (programmable option): Bell will "bing" at the end of any BA
group’s exit delay for Local systems. Alternately, for CCC connected systems,
bell will "bing" at end of exit delay as an indication that closing has been
acknowledged by the CCC.
•
Closing Trouble Bell (programmable option): Bell will ring for 5 minutes if
customer has turned the BA group On and has exited, but has failed to close the
exit door and exit delay has expired. Used to remind customer to re-enter the
premises and turn the BA group off, and re-exit the premises properly. Failure
to do so will result in an entry alarm.
∗
Start of bell can be delayed up to 255 minutes (1-minute increments).
UL
The start of bell ringing delay may not be programmed for UL Burglary alarm systems.
Description
Function
Access
Control
Used for controlling access to any selected BA group by having the output operate a
door strike. The output is normally locked. It operates for 10 seconds when valid ID
is entered at the operating panel if BA group is Off or when BA group is turned Off.
Summary of Contents for Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Page 2: ......
Page 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Page 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Page 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Page 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Page 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Page 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Page 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Page 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Page 210: ...Index Index 6...
Page 214: ...A 4...