![ADT Commercial Fire & Burglary Alarm System FOCUS 200 PLUS Installation And Setup Manual Download Page 108](http://html1.mh-extra.com/html/adt/commercial-fire-and-burglary-alarm-system-focus-200-plus/commercial-fire-and-burglary-alarm-system-focus-200-plus_installation-and-setup-manual_2854006108.webp)
FOCUS 200 PLUS Installation and Setup Guide
10-22
Symptom
Probable Cause
Corrective Action
1
Set screws on Keylok are
preventing key from
turning.
1
Using a 1/16” allen wrench, unscrew (in
counterclockwise direction) the left and/or right (not
center) set screw(s) on top of the Keylok cylinder until
lock core turns freely in the desired direction(s).
Marlok Construction key
causes green LED on
Keylok to light, but key
does not turn.
2
Keylok is defective.
2
Replace Keylok.
1
ACIU battery missing or is
low.
1
Install a fully charged battery. Make sure Jumper E11
is out.
2
Incorrect wiring from
ACIU to strike.
2
Check strike wiring to TB3-1 (-) and TB3-2 (+). Check
wiring for opens, shorts, and grounds.
3
Jumper E11 is OUT.
3
Insert Jumper E11.
4
Wrong strike.
4
Replace strike with one rated for 12VDC @ 550mA.
5
Excessive voltage drop on
strike wires.
5
Check strike wire guage and length. Strike wire should
be 18 AWG minimum and length should not exceed
150'.
6
Bad strike.
6
Connect strike directly to 12VDC battery. If strike does
not operate, replace strike.
Construction card causes
green LED on reader to
light, but strike does not
activate.
7
Bad ACIU.
7
Disconnect all wires from TB3-1 (-) and TB3-2 (+) of
ACIU. If 12VDC is not read across these terminals for
10 seconds after card is swiped, replace ACIU.
1
Improper or defective card.
1
Card must be compatible with reader. Card should not
be cracked. Mag stripe cards should not be subjected to
strong magnetic fields. Try using a known good card.
Red LED on reader does
not “wink” off when user
card/key is
swiped/inserted.
2
DIP switch in reader not
set for operation with
FOCUS control panel.
2
Refer to Summary of Access Control Card/Key Readers
chart for proper DIP switch settings.
Yellow LED on ACIU does
not flash.
ACIU tamper is installed and
is normal.
Release tamper.
1
ACIU is addressed
incorrectly.
1
Make sure ACIU is addressed for Communication
Group 4 and with a unique Unit Number (0-7).
2
RS-485 terminating
Jumper E1 is not being
used properly.
2
Remove Jumper E1 from all devices on the RS-485 bus
except the two end devices.
3
Incorrect wiring from
ACIU to control unit.
3
Check wiring to TB1-3 (yellow wire) and TB1-4 (blue
wire).
Cardreader (ACIU) Comm
Fail.
4
Bad ACIU
4
Connect ACIU directly to control unit. If Comm Fail
persists, replace ACIU.
1
Incorrect wiring from
ACIU to strike.
1
Check wiring from TB3-1 (-) and TB3-2 (+) to strike
and correct, if necessary.
2
No strike installed.
2
ACIU supervises the strike. If you are using some door-
releasing device other than a strike, connect a standard
3K EOLR across TB3-1 and TB3-2.
Cardreader (ACIU)
trouble.
3
Battery in ACIU is weak.
3
Check if battery is connected and check voltage. If
voltage is low, check that input voltage from RS-485 is
greater than 12.5VDC. If bus voltage is not OK, add a
power supply. If bus voltage is OK, let battery charge
for several minutes. If voltage does not increase, check
for 12VDC minimum at battery terminals on ACIU
with battery disconnected. If voltage is not OK, replace
ACIU.
Summary of Contents for Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Page 2: ......
Page 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Page 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Page 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Page 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Page 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Page 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Page 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Page 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Page 210: ...Index Index 6...
Page 214: ...A 4...