FOCUS 200 PLUS Installation and Setup Guide
6-2
Output Functions
UL
•
Commercial burglary alarm systems require bell circuits to be programmed for a minimum timeout of
16 minutes.
•
Commercial fire alarm systems require bell or indicating circuits to be supervised. Polarized fire-
indicating devices must be used.
•
Commercial fire alarm systems require bell or indicating circuits to be programmed for a minimum
timeout of 5 minutes.
•
Residential fire alarm systems require bell or indicating circuits to be programmed for a minimum
timeout of 4 minutes.
Each output can be programmed for one of the following functions:
Description
Function
Fire Alarm
The output activates and latches when an alarm occurs at any fire alarm point. If
all fire alarm points have restored to normal, the output resets by entering a
RESET command at any operating panel.
Note: It takes 40 seconds before the output resets.
Holdup
Alarm
The output activates when either of the following occurs:
•
An alarm condition occurs at a holdup point. It resets when the holdup device is
restored.
•
A hostage ID code is entered. The output resets when the operating panel
deactivates (after 45 seconds).
Supervisory
Alarm
The output activates when an alarm condition occurs at any supervisory point. It
resets when all supervisory devices are restored.
Alarm in any
BA Group
The output activates when an entry alarm occurs in any BA group during Nite Set.
The output resets when the involved BA group is changed to Day Set. This form of
output control can be used for direct-connect type applications.
Alarm in a
Selected BA
Group
This is the same as the above option except that it is used for an alarm in a single
selected BA group rather than for any BA group.
BA1 Alarm
Output is normally operated. It releases when an entry alarm occurs in BA1 during
Nite Set. It returns to operated condition when either the programmed bell time
ends and the points are secure or when BA1 is returned to Day Set.
BA2 Alarm
Same function as BA1 Alarm, except it relates to BA2.
BA3 Alarm
Same function as BA1 Alarm, except it relates to BA3.
BA4 Alarm
Same function as BA1 Alarm, except it relates to BA4.
BA5 Alarm
Same function as BA1 Alarm, except it relates to BA5.
BA6 Alarm
Same function as BA1 Alarm, except it relates to BA6.
BA7 Alarm
Same function as BA1 Alarm, except it relates to BA7.
BA8 Alarm
Same function as BA1 Alarm, except it relates to BA8.
Summary of Contents for Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Page 2: ......
Page 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Page 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Page 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Page 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Page 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Page 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Page 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Page 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Page 210: ...Index Index 6...
Page 214: ...A 4...