Section 14 – Programming
14-7
< ? Grp0 Ut0 Keypad
< BA-
❙
❙
❙
❙
❙
❙
❙
❙
< Previous
Change >
< Quit
Next >
This screen shows which BA Groups will be automatically opened
(turned off) when a valid ID Code is entered at the operating panel
indicated.
Select Change to edit the selections. Enter the number of each BA
Group that will turn off. Entering the number again will erase the
selection.
Select Next to move to the operating panel at the next address on
the RS-485 bus.
Continue until all operating panels have been programmed.
< ? Grp4 Ut0 Cardrdr
< BA-
❙
❙
❙
❙
❙
❙
❙
❙
Lg (N) >
< Previous
Change >
< Quit
Next >
Selecting Next at the last operating panel will bring you to this
screen.
This screen is same as the one for the operating panels, except this
is for BA Groups linked to card/key readers.
Select Change to edit the selections.
Select Next to move to the card/key reader at the next address on
the RS-485 bus.
Selecting Lg will toggle between Yes (Y) and No (N) to log
successful attempts, unsuccessful attempts, openings, and closings
at this card/key reader in the history log.
Selecting Next at the screen showing the last card/key reader will
bring you to the Point Data Info Screen.
Select Quit to return to Action Menu #4.
Programming the System Communication Options
Enter the program mode by entering the Service Code at the operating panel.
< ? Enter choice:
< Lesson
Turn on >
< See alarms
Reset >
< Quit
More >
Action Menu #1 is displayed.
Select More three times.
< ? Enter choice:
< Sys info
ID codes >
< Name pnt/gps
Load >
< Previous
First >
Action Menu #4 is displayed.
Select Load to continue.
< ?
SS-GG-IIII >
< ST P#
Remote DLL >
< DTM/Lst
Local DLL >
< Quit
More >
The Communication Screen is displayed.
Select More to program the CCC phone number.
< ? Pri Num/Hex Edi
< Pri Phone Num
< Pls/Lst
CID >
< Quit
Hex Data >
The CCC Options Screen is displayed.
Select the Pls/Lst key to scroll through the dialing methods. The
choices are:
Pls/Lst = Pulse dialing and loop start
Dtm/Lst = TouchTone dialing and loop start
Pls/Gndst = Pulse and ground start
Dtm/Gndst = TouchTone and ground start
Select the CID key to toggle between Contact ID (CID) and
Security Industry Association (SIA) formats.
Select Pri Phone Num to program the primary CCC phone
number.
Select Hex Data to program the hex data information.
Summary of Contents for Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Page 2: ......
Page 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Page 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Page 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Page 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Page 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Page 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Page 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Page 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Page 210: ...Index Index 6...
Page 214: ...A 4...