![ADT Commercial Fire & Burglary Alarm System FOCUS 200 PLUS Installation And Setup Manual Download Page 83](http://html1.mh-extra.com/html/adt/commercial-fire-and-burglary-alarm-system-focus-200-plus/commercial-fire-and-burglary-alarm-system-focus-200-plus_installation-and-setup-manual_2854006083.webp)
Section 9 – J5 Output Triggers
9-3
Entry
Number
Description
Function
26 (TSC)
BA Bell and
Vault Sensor
Test
Output turns on for 30 seconds when a test of the local bell and/or
vault sensors is commanded from the operating panel. When used in
conjunction with the testing of vault sensors, the output can be used
to turn on the test signal transmitter of a vault vibration sensor
system, and/or turn on the test sounder of a vault audio system.
33 (STC)
System
Trouble
Output turns on for any of the following conditions and remains on
until the condition is cleared:
•
A point has been installed, but the point has not been properly
entered into the control unit database.
•
A "comm fail" occurs for a point, an operating panel, or a printer
interface unit.
•
A tamper condition occurs at a Holdup-type point, a keyswitch
interface, a Remote Bell-type point, an Ambush Start-or End-
type point, or a Remote Power Supply-type point.
•
A trouble condition occurs at a Janitor Keyswitch-type point.
34 (PLC)
Point Link
Output will follow the status of a designated input point, or the
output of a designated Point Link output point.
37 (ACC)
BA Access
Output turns on for 10 seconds when:
•
A valid ID code is entered at the operating panel during the Day
Set condition of the associated BA group.
•
The BA group is turned to Day Set. A typical application is
having the output control a door-strike release mechanism,
permitting access to a controlled area.
38 (HST)
Horn/Strobe
(SIM
Gateway
only)
For use with a horn/strobe that will operate for an FA alarm and,
optionally, also for a BA alarm, as follows:
•
For an FA alarm, strobe will flash continuously and horn will
operate for an ongoing series of five 1-second rings followed by a
5-second pause. Horn/strobe can be silenced only after all FA
points become normal by entering any valid ID code (or
2,2,2,2,2,2); otherwise, turn-off will occur when 10-minute
timeout expires.
•
For a BA alarm, horn will sound continuously unless silenced by
entering a valid ID code (or automatic turn-off occurs for the BA
group that is involved). Strobe will not operate for a BA alarm.
Note: Set option 3 for NFPA temporal pattern (Yes) for this output
point type.
59 (ACD)
Access
Denied
This output point can be used to trigger a camera or activate an
annunciation device in the event that someone uses a card/key
having a code that either:
•
Is not in the system.
•
Does not have Irregular Open, Open, or Close access to all BA
groups associated with that ACIU.
•
Does not have the Irregular Open or Open option for any of the
associated BA groups that may be On.
•
Has a Close option and the person attempts to enter outside of
the scheduled Open period even though the associated protection
is Off.
When the point is triggered, the output will stay on for 10 seconds
and then go off.
Summary of Contents for Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Page 2: ......
Page 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Page 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Page 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Page 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Page 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Page 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Page 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Page 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Page 210: ...Index Index 6...
Page 214: ...A 4...