Section 14 – Programming
14-5
< ? FRONT DOOR 20
IS _____
Continue >
OPTION 2
< Previous
Change >
This is Option 2 Screen.
The function of Option 2 changes depending on the type of point
being used.
For Input Point Types 1 to 8, 10, 11, 13, 35, 60, 64 = N/C
Contact:
Select whether a normally closed contact is used. If so, an open in
the loop wiring will be ignored during the Day Set, but will initiate
an alarm during the Nite Set.
For Output Point Type 34 = Output Link:
Select whether this output will follow the status of a designated
output point.
For Output Point Types 27, 38 = Common BA:
Select whether the output will be turned on by an alarm in only
one BA group or by an alarm in any one of a series of BA groups.
For All BA RF transmitters option 2 must be enabled (IS).
Select Change to toggle the option.
Select Continue to save the selection and move to the next option
screen.
< ? FRONT DOOR 20
IS _____
Continue >
OPTION 3
< Previous
Change >
This is Option 3 Screen.
The function of Option 3 changes depending on the type of point
being used.
For Input Point Types 1 to 9, 13 = Self-Test:
Select whether the device will perform a self-test. This is for
devices with a built-in SIM that have self-test capability.
For Input Point Types 10, 11 = Latch Contact:
Select whether a momentary contact is used on the loop to initiate
an alarm.
For Input Point Types 60, 64 =SIM:
Select whether the pushbutton will be connected to a SIM
Gateway.
Select Change to toggle the option.
Select Continue to save the selection and move to the next screen.
< ? RF Point?
Continue >
No >
Yes >
This is the RF Programming Screen.
Select Continue if you do not desire to change the RF information
for this point.
Select No if the point is not an RF point.
Select Yes if the point is RF or if there is any information
concerning this point that needs to be changed. This will move you
to the RF Information Screen.
< ? RF information
< Type RF
Continue >
< Loop 1
< Previous
RF Information Screen is displayed.
Select Type to scroll through the choices (RF, UR, BR) for the
type of RF point.
Select Loop to scroll through the loops (1-4) for this point
Select Continue to save the info and move to the next screen.
< ? Enter User #
Continue >
BR User # _ _ _ 0
< Previous
Enter >
BR User # Screen is displayed.
If the type selected was BR, this screen is displayed.
Enter the User # associated with this RF transmitter.
Select Enter to save the user #. The Enter key changes to Delete.
Select Delete to erase the user # displayed.
Select Continue to move to the Hard ID Screen.
Summary of Contents for Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Page 2: ......
Page 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Page 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Page 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Page 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Page 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Page 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Page 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Page 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Page 210: ...Index Index 6...
Page 214: ...A 4...