Running flat cables
The flat cables from the platform can be run to the electrical cabinet in two ways depending on which
side of the mast the electrical cabinet will be placed.
• In both cases the flat cables shall be fastened with a cable reliever in aposition on the middle rear
beam, or the nearest rear beam above. In the example on the illustration below it is on the 4-th rear
beam. Do not tight the cable reliever too hard, the cables can be damaged. Use self tapping screws
M6x16 for the cable reliever.
Mount locking arms
• The locking arms shall be mounted on every floor, 300 mm above the floor height, see the drawing
for the lift to find the floor heights. It is fastened with two self drilling screws as in the illustration
below.
Fig. 17 Locking arm 300 mm above floor height
Running cables to the electrical cabinet
The two flat cables and two grey cables (emergency stop and door blocking) runs on the outside of the
rail to the electrical cabinet. It depends on where the electrical cabinet and the emergence stop are
placed, sometimes all four cables can be run together and sometimes they need to run on each side of
the mast.
• Mount the white holders for cable ties in the predrilled holes on the mast rail (-s), as many as needed
to reach the electrical cabinet.
• Fasten the cables with cable ties. Don´t twist the cables.
Fig. 18 Running cables
Mount the electrical cabinet
7000 100 en-GB AD
41
Summary of Contents for 7000
Page 1: ...Vector Installation Manual HQ ...
Page 23: ...ASSEMBLY 5 ASSEMBLY 5 1 FIXINGS 7000 100 en GB AD 19 ...
Page 25: ...ASSEMBLY Fig 15 Mast preparation before installation 7000 100 en GB AD 21 ...
Page 27: ...ASSEMBLY Lift the top section 7000 100 en GB AD 23 ...
Page 33: ...ASSEMBLY 7000 100 en GB AD 29 ...
Page 34: ...ASSEMBLY 30 7000 100 en GB AD ...
Page 42: ...ASSEMBLY The mast shall stand upright the tolerance is Max 2 mm m 38 7000 100 en GB AD ...
Page 70: ...ASSEMBLY Fig 59 Mounting of Filled wall panels 66 7000 100 en GB AD ...
Page 72: ...ASSEMBLY Fig 61 Principal drawing Shaft corners 68 7000 100 en GB AD ...
Page 100: ...This page is intentionally left blank 96 7000 100 en GB AD ...
Page 117: ...OPTIONS Fig 126 Electrical connections external door opener 7000 100 en GB AD 113 ...
Page 140: ...This page is intentionally left blank 136 7000 100 en GB AD ...
Page 142: ...This page is intentionally left blank 138 7000 100 en GB AD ...