Functionality
The Minimum second pulse timer function TPSGAPC contains two independent
timers. The function has a settable pulse length (in seconds). The timers are used
for setting the minimum pulse length for example, the signal outputs. Once the
input is activated, the output is set for a specific duration using the
Pulse time
setting. Both timers use the same setting parameter.
Figure 62: A = Trip pulse is shorter than Pulse time setting, B = Trip pulse is longer
than Pulse time setting
Signals
TPSGAPC Input signals
Table 120: TPSGAPC Input signals
Name
Type
Default
Description
IN1
BOOLEAN
0=False
Input 1
IN2
BOOLEAN
0=False
Input 2
TPSGAPC Output signals
Table 121: TPSGAPC Output signals
Name
Type
Description
OUT1
BOOLEAN
Output 1 status
OUT2
BOOLEAN
Output 2 status
Settings
TPSGAPC Non group settings (Basic)
Table 122: TPSGAPC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Pulse time
0...300
s
1
0
Minimum pulse
time
Basic functions
1MRS758407 C
100
SMU615
Technical Manual
Summary of Contents for Relion SMU615
Page 1: ... RELION Substation Merging Unit SMU615 Technical Manual ...
Page 2: ......