Parameter
Values (Range)
Unit
Step
Default
Description
32=UL1
33=UL2
34=UL3
35=U12B
36=U23B
37=U31B
38=UL1B
39=UL2B
40=UL3B
Channel id text
0 to 64 characters, al-
phanumeric
DR analog
channel X
Identification text for the analog
channel used in the COMTRADE
format
High trigger level
0.00...60.00
pu
0.01
10.00
High trigger level for the analog
channel
Low trigger level
0.00...2.00
pu
0.01
0.00
Low trigger level for the analog
channel
Storage mode
0=Waveform
1=Trend / cycle
1
0
Storage mode for the analog
channel
7.2.6
Monitored data
7.2.6.1
Monitored data
Table 254: RDRE Monitored data
Parameter
Values
(Range)
Unit
Step
Default
Description
Number of re-
cordings
0...100
Number of re-
cordings cur-
rently in
memory
Rem. amount
of rec.
0...100
Remaining
amount of re-
cordings that
fit into the
available re-
cording mem-
ory, when cur-
rent settings
are used
Rec. memory
used
0...100
%
Storage mode
for the binary
channel
Time to trig-
ger
0...604 800
s
Time remain-
ing to the
next periodic
triggering
1MRS758407 C
Measurement functions
SMU615
Technical Manual
227